2019-10-03 15:16:25 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1- THIS HOUSE WAS BUILT UNDER PERMIT #05031759. |
| ACCORDING TO CITY RECORDS, PLANS SHOW THAT THE SECOND |
| FLOOR WAS LEFT UNFINISHED. BASED ON CITY PLANS THERE IS |
| DOOR LEADING FROM THE GARAGE TO THE ROOM ABOVE. |
| OPENINGS FROM THE GARAGE TO A ROOM THAT CAN BE USED FOR |
| SLEEPING PURPOSES IS NOT ALLOWED. REVISE PLANS AS |
| REQUIRED. SEC. 801.3 FBC-EXISTING BUILDING AND SEC. |
| R302.5.1 FBC-RESIDENTIAL. |
| |
| 2- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING |
| TO THE SECOND FLOOR TO SHOW COMPLIANCE WITH THE OPENING |
| PROTECTION OF SEC. 801.3 FBC-EXISTING BUILDING AND SEC. |
| R302.5.1 FBC-RESIDENTIAL. |
| |
| 3- NEED TO SHOW COMPLIANCE WITH THE EGRESS REQUIREMENTS |
| WITHOUT TRAVELING THROUGH THE GARAGE. PROVIDE PLANS |
| SHOWING THE EGRESS FROM THE SECOND FLOOR TO THE OUTSIDE |
| OF THE STRUCTURE. SEC. 801.3 FBC-EXISTING BUILDING AND |
| SEC. R311.1 FBC-RESIDENTIAL. |
| |
| 4- SPECIFY THE HEADROOM IN STAIRWAY AS REQUIRED BY SEC. |
| R311.7.2 FBC-RESIDENTIAL. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED: |
| A) ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| THE OWNER PRIOR TO RECEIVE THE PERMIT. AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION |
| (2017). |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| C)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE RATIO |
| IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR, |
| PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE |
| 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC. |
| R806.2. |
| |
| D) REVISE ITEM #4 ON PAGE 1 OF 4 TO MATCH PLANS. |
| ACCORDING TO PLANS SUBMITTED. THIS STUDIO IS USED AS |
| ONE BEDROOM. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF |
| VALUATION SIGNED CONTRACTS INCLUDING DESIGN |
| PROFESSIONAL FEES. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |