2019-10-04 17:19:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090742
 10/4/19
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW
 ADDITION- SECTION R101.5 FBC EC.
  
 2) GAS DRYER:
  
 A) SUBMIT SPECS FOR THE DRYER- SECTION G2408.1 FBC RES.
  
 B) PROVIDE A GAS PIPING ISOMETRIC DRAWING- SECTION
 G2413.1 FBC RES.
  
 C) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SECTION G2407.1 FBC RES.
  
 D) PROVIDE DRYER VENTING PLANS- SECTION G2427.1 FBC
 RES.
  
 3) PROVIDE A TOILET EXHAUST FAN SCHEDULE AND SHOW THE
 EXHAUST DUCT RUN AND TERMINATION LOCATION- SECTION
 M1501.1 & M1507.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  