2019-10-09 15:43:14 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| ALARMS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. IF NONE |
| ARE EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. |
| FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| 2. THE CIRCUIT FOR THE RECEPTACLE OUTLET LOCATED IN THE |
| POWDER ROOM IS NOT DETAILED. A MINIMUM OF ONE 20 AMPERE |
| BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE |
| E3703.4 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |