Plan Review Notes
Plan Review Notes For Permit 19090742
Permit Number 19090742
Review Stop E
Sequence Number 1
Notes
Date Text
2019-10-09 15:43:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. IF NONE
 ARE EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS.
 FBC RE R314.3, R315.1; WPB FBC 107.2.1
 2. THE CIRCUIT FOR THE RECEPTACLE OUTLET LOCATED IN THE
 POWDER ROOM IS NOT DETAILED. A MINIMUM OF ONE 20 AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE
 E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  