2019-09-20 07:11:3709/20/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. PROVIDE MANUFACTURES SPECIFICATION FOR GENERATOR,
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 2. SHOW DRIP LEG ON EQUIPMENT, IF INSTALLED INSIDE
 GENERATOR PLEASE NOTE ON ISOMETRIC PER THE 2017 FBC
 RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
 3. AN ELECTRICAL PERMIT IS REQUIRED FOR THE GENERATOR
 BY A LICENSED CONTRACTOR PER THE WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  