2019-10-21 09:06:31PROVISO- REVIEWED REMOTELY BY TIM HUNT
  
 1) SHT-A2.1.1*SHOWER HEAD SHALL BE MAX FIX 48? OR ON A
 SLIDE BAR WITH THE GRIPPING SURFACE @ MAX 48?. FBC-ACC
 608.5.1
 2) SHT-P3 ALL NEW HOT AND RETURN WATER PIPING SHALL BE
 INSULATED WITH 1? WALL MIN. FBC-PLB 607.5, FBC-ENERGY
 C404.4
 3) SHT-P-3 MIRROR DETAIL ADDED 40? MAX IS TO THE
 REFLECTIVE SURFACE OF THE MIRROR AND NOT THE BOTTOM
 EDGE OR TRIM. FBC-ACC 603.3
  
  
  