Plan Review Notes
Plan Review Notes For Permit 19090543
Permit Number 19090543
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-23 15:04:131) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIIONS FOR THE HEAT PUMP. THE HEAT PUMP SHALL
 HAVE A MINIMUM COP OF 4.0 PER THE FBC-ENERGY
 SEC.R403.10.5, WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE MAIN DRAIN. THA MAXIMUM
 GPM DETERMINED BY THE TOTAL DYNAMIC HEAD AND THE POOL
 PUMP CURVE SHALL NOT EXCEED THE MAXIMUM GPM FLOW
 THROUGH THE MAIN DRAIN PER APSP 7, WPB AMEND. TO FBC
 SEC. 107..2.1.
 3) PLOT THE TDH AND FLOW ON THE POOL PUMP CURVE.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW