Plan Review Notes
Plan Review Notes For Permit 19090440
Permit Number 19090440
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2019-10-07 10:56:48NFIP REVIEW - ELEVATION CERTIFICATE
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. EC FOR ACCESSORY STRUCTURE.
  
 1A. COMPLETE SECTION C2 (E) LOWEST ELEVATION OF
 MACHINERY OR EQUIPMENT.
 1B. ELEVATION CERTIFICATE IS BASED ON A FIRM. DESIGN
 FLOOD ELEVATION (DFE) OF C2 (E) SHALL BE 8.4 FEET NAVD.
 YOU MAY WISH TO UTILIZE THE FLOOD INSURANCE STUDY. THIS
 DFE WOULD BE 8.3 FEET NAVD BASED ON TRANSECT LINE 11 OF
 THE FIS.
  
 2. EC FOR NEW SINGLE FAMILY RESIDENCE.
  
 2A. THE BASE FLOOD ELEVATION (BFE) WAS ESTABLISHED BY A
 FLOOD INSURANCE RATE MAP. THIS ELVATION IS STATED AS 6
 & 7 FEET NAVD IN SECTION B9 OF THE ELVATION CERTIFICATE
 (EC). THIS ELEVATION SHALL BE SET AT 7.4 FEET UNLESS A
 FLOOD INSURANCE STUDY (FIS) IS USED TO ESTABLISH THE
 BFE.
 2B. THE BFE BASED ON THE FIS SHALL BE SET AT 7.3 FEET
 NAVD BASED ON THE PARCEL'S LOCATION TO TRANSECT LINE
 #11 OF THE FIS DATED OCT. 5, 2017.
 2C. DUE TO THE CITY'S REQUIREMENT OF A TWO FOOT
 FREEBOARD THE DFE SHALL BE 9.3 FEET NAVD.
 2S. TOP OF SLAB IS SHOWN AS 8.83 FEET NAVD WITH A 2
 INCH ALLOWANCE FOR FLOORING.
 2D. THE FINISHED FLOOR ELEVATION IS 9.0 FEET NAVD AS
 STATED ON THE CONSTRUCTION DRAWINGS.
  
 3. SECTION C2(E) IS REQUIRED.
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy