2019-09-12 15:43:14 | COMMENTS TRANSFERRED FROM 19080288 (MAIN HOUSE |
| ADDITION) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE ON RISER DIAGRAM STATES THAT LIGHTING IN |
| CLOSETS TO COMPLY WITH 410-8. THIS CODE SECTION DOES |
| NOT APPLY TO LIGHTING IN CLOSETS. PROVIDE CORRECTION. |
| NEC 410.16; FBC RE E4003.12 |
| 2. NOTE IN ELECTRICAL NOTES STATES THAT RECEPTACLES |
| SHALL BE TAMPER RESISTANT PER NEC 406.11. THIS CODE |
| SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. |
| NOTE ALSO QUOTES THE 2007 FBC AS CODE REFERENCE, WHICH |
| IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC |
| 406.12; FBC RE E4002.14; FBC PREFACE, WPB FBC 107.2.1 |
| 3. NOTE STATES THAT ALL BREAKERS SHALL HAVE AN AIC |
| RATING OF 1000. PROVIDE CORRECTION. FBC RE E3606.3 |
| 4. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| 801.2, OR 901.2 AS APPLICABLE. |
| 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| FBC EC C405.1, R404.1 |
| 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE |
| RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR |
| PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON |
| THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE |
| CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6 |
| 7. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |