Plan Review Notes
Plan Review Notes For Permit 19090434
Permit Number 19090434
Review Stop E
Sequence Number 1
Notes
Date Text
2019-09-12 15:43:14COMMENTS TRANSFERRED FROM 19080288 (MAIN HOUSE
 ADDITION)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE ON RISER DIAGRAM STATES THAT LIGHTING IN
 CLOSETS TO COMPLY WITH 410-8. THIS CODE SECTION DOES
 NOT APPLY TO LIGHTING IN CLOSETS. PROVIDE CORRECTION.
 NEC 410.16; FBC RE E4003.12
 2. NOTE IN ELECTRICAL NOTES STATES THAT RECEPTACLES
 SHALL BE TAMPER RESISTANT PER NEC 406.11. THIS CODE
 SECTION DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES.
 NOTE ALSO QUOTES THE 2007 FBC AS CODE REFERENCE, WHICH
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14; FBC PREFACE, WPB FBC 107.2.1
 3. NOTE STATES THAT ALL BREAKERS SHALL HAVE AN AIC
 RATING OF 1000. PROVIDE CORRECTION. FBC RE E3606.3
 4. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6
 7. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  