2019-12-10 06:08:12PLUMBING 2ND REVIEW**DENIED**19090403
 1) SHT. AE501 TOILET DETAIL SHOWS SIDE GRAB BAR OVERALL
 AS 52? AND NOT THE REQUIRED MIN OF 54?. FBC-ACC 604.5.1
 2) PROVIDE THE GREASE INTERCEPTOR SIZING CALCULATIONS
 BASE ON YOUR PDI G 101 . FBC 107.3.5
 3) PROVIDE GREASE INTERCEPTOR INSTALLATION MANUAL. FBC
 107.1
  