Plan Review Notes
Plan Review Notes For Permit 19090403
Permit Number 19090403
Review Stop G
Sequence Number 2
Notes
Date Text
2019-12-10 06:08:44GAS 2ND REVIEW**DENIED**19090403
 1) TERMINATION OF WATER HEATER VENT DOES NOT SHOW
 ANCHORING OR INTAKE VENT. PLEASE CLARIFY. FBC 107.2.1
 2) DEFERRED SUBMITTAL ON GAS EQUIPMENT IS NOT PERMITTED
 AND MUST BE SUBMITTED FOR THIS PLAN REVIEW. AS I
 EXPLAINED OVER THE PHONE AFTER THE 1ST REVIEW THIS
 WOULD NEED TO BE APPROVE BY THE CHIEF PLUMBING
 INSPECTOR (TIM LARGE) WHICH TO DATE HAS NOT HAPPENED.
 SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3.GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1
 3) PROVIDE SIZING CHARTS FOR SYSTEM AFTER THE PRESSURE
 REDUCING REGULATORS. SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37)
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE INSIDE
 OF THE BUILDING SHALL BE APPROVED FOR INDOOR
 INSTALLATION. PROVIDE VENTING OF EACH REGULATOR. DOES
 NOT MATTER WHO IS SUPPLYING THEM BUT THE INSTALLATION
 MANUAL IS REQUIRED FOR THIS REVIEW. 2017 FGC SEC.410.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)