2019-12-10 06:08:44 | GAS 2ND REVIEW**DENIED**19090403 |
| 1) TERMINATION OF WATER HEATER VENT DOES NOT SHOW |
| ANCHORING OR INTAKE VENT. PLEASE CLARIFY. FBC 107.2.1 |
| 2) DEFERRED SUBMITTAL ON GAS EQUIPMENT IS NOT PERMITTED |
| AND MUST BE SUBMITTED FOR THIS PLAN REVIEW. AS I |
| EXPLAINED OVER THE PHONE AFTER THE 1ST REVIEW THIS |
| WOULD NEED TO BE APPROVE BY THE CHIEF PLUMBING |
| INSPECTOR (TIM LARGE) WHICH TO DATE HAS NOT HAPPENED. |
| SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3.GAS |
| APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| SEC.305.1 |
| 3) PROVIDE SIZING CHARTS FOR SYSTEM AFTER THE PRESSURE |
| REDUCING REGULATORS. SUBMIT TWO COPIES OF THE |
| APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR |
| PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| TABLES 402.4 (1) THRU 402.4 (37) |
| 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE INSIDE |
| OF THE BUILDING SHALL BE APPROVED FOR INDOOR |
| INSTALLATION. PROVIDE VENTING OF EACH REGULATOR. DOES |
| NOT MATTER WHO IS SUPPLYING THEM BUT THE INSTALLATION |
| MANUAL IS REQUIRED FOR THIS REVIEW. 2017 FGC SEC.410.1 |
| |
| |