Plan Review Notes
Plan Review Notes For Permit 19090403
Permit Number 19090403
Review Stop P
Sequence Number 1
Notes
Date Text
2019-10-16 05:55:04PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE CLEAR FLOOR SPACE FOR ALL TOILET ROOMS
 SHOWING THE INTENT TO MEET FLORIDA ACCESSIBILITY. FBC
 107.3.5
 2) SHT. AE-504 SHOWS THE MIRROR MOUNTING 40? TO THE
 BOTTOM EDGE. THE MAX 40? IS TO THE REFLECTIVE SURFACE
 OF THE MIRROR. FBC-ACC 603.3
 3) PROVIDE CABINET DETAIL SHOWING THE COPY ROOM SINKS
 E129 AND E202 WILL MEET FLORIDA ACCESSIBILITY FOR CLEAR
 FLOOR SPACE AND HEIGHT MAX 34?. FBC-ACC 606.3, 606.3
 4) SHT. P-16 IS MISSING THE REQUIRED SHUT OFF VALVE ON
 THE SUMP PUMP. FBC-PLB 712.2
 5) PROVIDE HOW YOU DETERMINE THE SIZE OF THE GREASE
 INTERCEPTOR EITHER BY PDI G 101 OR 64E-6
 6) SHT. P-16 UNDER NOTE #1 PLEASE ADD THAT THE MIXING
 VALVE SHALL BE AN ASSE 1070 APPROVED DEVICE. FBC-PLB
 607.1.2
 7) SHT.P-10 AND P-11 ARE MISSING WATER ISOMETRIC ARE
 MISSING THE REQUIRED SHUT OFF VALVES ON ALL DOWN FEEDS.
 FBC-PLB 606.1 (5)
 8) PROVIDE LOCATION OF THE HI-LOW DRINKING FOUNTAIN AS
 REQUIRED IN FBC-PLB 410.3
  
 TIM HUNT
 PLUMBING PLANS EXAMINER