Plan Review Notes For Permit 19090403 |
Permit Number |
19090403 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-16 05:55:04 | PLUMBING 1ST REVIEW**DENIED** | | | | 1) PROVIDE CLEAR FLOOR SPACE FOR ALL TOILET ROOMS | | SHOWING THE INTENT TO MEET FLORIDA ACCESSIBILITY. FBC | | 107.3.5 | | 2) SHT. AE-504 SHOWS THE MIRROR MOUNTING 40? TO THE | | BOTTOM EDGE. THE MAX 40? IS TO THE REFLECTIVE SURFACE | | OF THE MIRROR. FBC-ACC 603.3 | | 3) PROVIDE CABINET DETAIL SHOWING THE COPY ROOM SINKS | | E129 AND E202 WILL MEET FLORIDA ACCESSIBILITY FOR CLEAR | | FLOOR SPACE AND HEIGHT MAX 34?. FBC-ACC 606.3, 606.3 | | 4) SHT. P-16 IS MISSING THE REQUIRED SHUT OFF VALVE ON | | THE SUMP PUMP. FBC-PLB 712.2 | | 5) PROVIDE HOW YOU DETERMINE THE SIZE OF THE GREASE | | INTERCEPTOR EITHER BY PDI G 101 OR 64E-6 | | 6) SHT. P-16 UNDER NOTE #1 PLEASE ADD THAT THE MIXING | | VALVE SHALL BE AN ASSE 1070 APPROVED DEVICE. FBC-PLB | | 607.1.2 | | 7) SHT.P-10 AND P-11 ARE MISSING WATER ISOMETRIC ARE | | MISSING THE REQUIRED SHUT OFF VALVES ON ALL DOWN FEEDS. | | FBC-PLB 606.1 (5) | | 8) PROVIDE LOCATION OF THE HI-LOW DRINKING FOUNTAIN AS | | REQUIRED IN FBC-PLB 410.3 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | [email protected] | | 561-248-2703 | | |
|