Plan Review Notes
Plan Review Notes For Permit 19090403
Permit Number 19090403
Review Stop M
Sequence Number 1
Notes
Date Text
2019-10-09 17:25:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19090403
 10/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6 & M7: PLEASE PROVIDE SYMBOLS TO SHOW THE
 LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE
 SUPPLY SYSTEMS OF AHU 1.10 & 1.11- SECTION 606.2.1 FBC
 M.
  
 2) M7: LABEL THE SUPPLY DROP FROM AHU-1.11 AND PROVIDE
 THE DUCT DIMENSIONS- SECTION 107.2.1 WPB.
  
 3) G1102, M6, & M7: A FIRE DAMPER IS REQUIRED AT THE
 PENETRATION OF THE DUCT RISER FROM AHU-1.11 THROUGH THE
 FIRE-RATED FLOOR CEILING ASSEMBLY- SECTION 607.2.1 FBC
 M.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS)
 FOR THE NEW COOKING APPLIANCES- SECTION 623.1 FBC-FG,
 AND PROVIDE COMBUSTION AIR CALCULATIONS ON THE PLAN-
 SECTION 304 FG.
  
 5) PROVIDE WINDLIOAD ENGINEERING FOR INSTALLATION OF
 THE ROOFTOP AC SYSTEM- SECTION 301.15 FBC M.
  
 6) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS, FIRE SUPPRESSION SYSTEMS, AND WALKIN COOLERS AND
 FREEZERS- SECTION 107.2.1 WPB. PLEASE NOTE THE
 FOLLOWING ITEMS PERTAINING TO THE HOOD PERMIT. A) SHEET
 M9: IT APPEARS THAT THE DISCHARGE FROM THE GREASE
 EXHAUST FANS WILL BE WITHIN THE REQUIRED 10' CLEARANCE
 TO THE PARAPET WALL- SECTION 506.3.1.3.3 UNLESS MEETING
 THE EXCEPTION TO THAT SECTION. B) THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE EXHAUST HOOD MAKEUP AIR AND
 THE AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F- SECTION 508.1.1
  
 7) COMMISSIONING OF THE MECHANICAL, SERVICE WATER
 HEATING SYSTEMS, AND AUTOMATIC LIGHTING SYSTEM CONTROLS
 IS REQUIRED PER SECTION C408.2 FBC-17 ENERGY
 CONSERVATION. SUBMIT A COMMISSIONING PLAN AS OUTLINED
 IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2-
 C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT
 FINAL INSPECTION, ALONG WITH A LETTER FROM THE BUILDING
 OWNWERSHIP ACKNOWLEDGING RECEIPT OF THE REPORT.
  
 8) DEFERRED SUBMITTALS: THE KITCHEN APPLIANCES, AND
 WINDLOAD ENGINEERING NOTED ABOVE MAY BE DEFERRED
 SUBMITTALS IF NECESSARY. PLEASE REVIEW THE REQUIRED
 SUBMITTALS LISTED BELOW THAT MAY ALSO BE DEFERRED.
  
 1) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 2) MOTORIZED O/A DAMPERS
 3) DUCT SMOKE DETECTORS
 4) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 5) AC STAND NOA?S OR FL. PRODUCT APPROVALS
 6) CO2 SENSORS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  