2019-10-09 17:25:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19090403 |
| 10/8/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M6 & M7: PLEASE PROVIDE SYMBOLS TO SHOW THE |
| LOCATIONS OF THE REQUIRED DUCT SMOKE DETECTORS IN THE |
| SUPPLY SYSTEMS OF AHU 1.10 & 1.11- SECTION 606.2.1 FBC |
| M. |
| |
| 2) M7: LABEL THE SUPPLY DROP FROM AHU-1.11 AND PROVIDE |
| THE DUCT DIMENSIONS- SECTION 107.2.1 WPB. |
| |
| 3) G1102, M6, & M7: A FIRE DAMPER IS REQUIRED AT THE |
| PENETRATION OF THE DUCT RISER FROM AHU-1.11 THROUGH THE |
| FIRE-RATED FLOOR CEILING ASSEMBLY- SECTION 607.2.1 FBC |
| M. |
| |
| 4) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS) |
| FOR THE NEW COOKING APPLIANCES- SECTION 623.1 FBC-FG, |
| AND PROVIDE COMBUSTION AIR CALCULATIONS ON THE PLAN- |
| SECTION 304 FG. |
| |
| 5) PROVIDE WINDLIOAD ENGINEERING FOR INSTALLATION OF |
| THE ROOFTOP AC SYSTEM- SECTION 301.15 FBC M. |
| |
| 6) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR KITCHEN |
| HOODS, FIRE SUPPRESSION SYSTEMS, AND WALKIN COOLERS AND |
| FREEZERS- SECTION 107.2.1 WPB. PLEASE NOTE THE |
| FOLLOWING ITEMS PERTAINING TO THE HOOD PERMIT. A) SHEET |
| M9: IT APPEARS THAT THE DISCHARGE FROM THE GREASE |
| EXHAUST FANS WILL BE WITHIN THE REQUIRED 10' CLEARANCE |
| TO THE PARAPET WALL- SECTION 506.3.1.3.3 UNLESS MEETING |
| THE EXCEPTION TO THAT SECTION. B) THE TEMPERATURE |
| DIFFERENTIAL BETWEEN THE EXHAUST HOOD MAKEUP AIR AND |
| THE AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| DEGREES F- SECTION 508.1.1 |
| |
| 7) COMMISSIONING OF THE MECHANICAL, SERVICE WATER |
| HEATING SYSTEMS, AND AUTOMATIC LIGHTING SYSTEM CONTROLS |
| IS REQUIRED PER SECTION C408.2 FBC-17 ENERGY |
| CONSERVATION. SUBMIT A COMMISSIONING PLAN AS OUTLINED |
| IN SECTION C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2- |
| C408.2.3.3. PLEASE NOTE THAT A COPY OF THE |
| COMMISSIONING REPORT SHALL BE SUBMITTED FOR REVIEW AT |
| FINAL INSPECTION, ALONG WITH A LETTER FROM THE BUILDING |
| OWNWERSHIP ACKNOWLEDGING RECEIPT OF THE REPORT. |
| |
| 8) DEFERRED SUBMITTALS: THE KITCHEN APPLIANCES, AND |
| WINDLOAD ENGINEERING NOTED ABOVE MAY BE DEFERRED |
| SUBMITTALS IF NECESSARY. PLEASE REVIEW THE REQUIRED |
| SUBMITTALS LISTED BELOW THAT MAY ALSO BE DEFERRED. |
| |
| 1) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. |
| 2) MOTORIZED O/A DAMPERS |
| 3) DUCT SMOKE DETECTORS |
| 4) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES |
| INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT |
| APPROVALS AND/OR MIAMI-DADE NOA'S |
| 5) AC STAND NOA?S OR FL. PRODUCT APPROVALS |
| 6) CO2 SENSORS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |