Plan Review Notes
Plan Review Notes For Permit 19090403
Permit Number 19090403
Review Stop G
Sequence Number 1
Notes
Date Text
2019-10-16 05:55:46GAS 1ST REVIEW**DENIED**
  
 1) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS.
 502 THRU 505
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR.
  
 4) PROVIDE SIZING TABLE FOR AFTER THE GAS REGULATOR
 .5LB SYSTEM. ) SUBMIT TWO COPIES OF THE APPLICABLE
 SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37)
  
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 6) ) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  