2019-10-02 08:49:04 | PLUMBING 1ST REVIEW**DENIED** |
| |
| 1) SHT. P5.6 STACK # 17 AND SHT. 5.7 STACK 32 AS THE |
| SHOWERS AND KITCHEN SHARING THE SAME VENT STACK. ONLY |
| OTHER BATHROOM FIXTURES ARE PERMITTED TO SHARE THE SAME |
| VERTICAL WET VENT. FBC-P 912.1.2 |
| 2) BACKFLOW FOR THE POOL MARK UP SHALL BE A LEAD FREE |
| RPZ AND NOT PVB AS CALLED OUT ON SHT. P6.2. BACKFLOWS |
| REQUIRED SEPARATE PERMITS BUT ALL BACKFLOWS CAN BE |
| PULLED UNDER 1 PERMIT. BACKFLOWS SHALL ONLY BE |
| INSTALLED BY LICENSE PLUMBING CONTRACTORS. 2017 CITY OF |
| WPB CROSS CONNECTION MANUAL. |
| 3) TANKLESS HWH CALLED OUT ON SHT. 6.2 DETAIL #2 MIXING |
| VALVE MUST BE AN APPROVED ASSE 1070 DEVICE. FBC-P |
| 607.1.2 |
| 4) ALL WATER HEATER DETAILS ON SHT. 6.2 CALL OUT ?? |
| WALL INSULATIONS ON THE HOT AND HOT WATER RETURN |
| PIPING. THE MIN THICKNESS ALLOWED IS 1? WALL THICKNESS. |
| FBC-P 607.5, FBC-ENERGY C404.4 |
| 5) BEING THAT A CHECK VALVE MUST BE INSTALLED ON THE |
| COLD WATER SUPPLY OF EACH HWH FOR THE HOT WATER RETURN |
| LINE THIS CREATES A CLOSED SYSTEM REQUIRED A THERMO |
| EXPANSION DEVICE. PROVIDE A MEANS OF THERMO EXPANSION |
| AS REQUIRED IN FBC-P 607.3. THIS COMMENT WAS ALSO ON |
| THE 1ST REVIEW OF THE SLAB PLAN REVIEW PERMIT # |
| 19030235 |