Plan Review Notes
Plan Review Notes For Permit 19090347
Permit Number 19090347
Review Stop P
Sequence Number 1
Notes
Date Text
2019-10-02 08:49:04PLUMBING 1ST REVIEW**DENIED**
  
 1) SHT. P5.6 STACK # 17 AND SHT. 5.7 STACK 32 AS THE
 SHOWERS AND KITCHEN SHARING THE SAME VENT STACK. ONLY
 OTHER BATHROOM FIXTURES ARE PERMITTED TO SHARE THE SAME
 VERTICAL WET VENT. FBC-P 912.1.2
 2) BACKFLOW FOR THE POOL MARK UP SHALL BE A LEAD FREE
 RPZ AND NOT PVB AS CALLED OUT ON SHT. P6.2. BACKFLOWS
 REQUIRED SEPARATE PERMITS BUT ALL BACKFLOWS CAN BE
 PULLED UNDER 1 PERMIT. BACKFLOWS SHALL ONLY BE
 INSTALLED BY LICENSE PLUMBING CONTRACTORS. 2017 CITY OF
 WPB CROSS CONNECTION MANUAL.
 3) TANKLESS HWH CALLED OUT ON SHT. 6.2 DETAIL #2 MIXING
 VALVE MUST BE AN APPROVED ASSE 1070 DEVICE. FBC-P
 607.1.2
 4) ALL WATER HEATER DETAILS ON SHT. 6.2 CALL OUT ??
 WALL INSULATIONS ON THE HOT AND HOT WATER RETURN
 PIPING. THE MIN THICKNESS ALLOWED IS 1? WALL THICKNESS.
 FBC-P 607.5, FBC-ENERGY C404.4
 5) BEING THAT A CHECK VALVE MUST BE INSTALLED ON THE
 COLD WATER SUPPLY OF EACH HWH FOR THE HOT WATER RETURN
 LINE THIS CREATES A CLOSED SYSTEM REQUIRED A THERMO
 EXPANSION DEVICE. PROVIDE A MEANS OF THERMO EXPANSION
 AS REQUIRED IN FBC-P 607.3. THIS COMMENT WAS ALSO ON
 THE 1ST REVIEW OF THE SLAB PLAN REVIEW PERMIT #
 19030235
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  