2019-09-27 17:17:2109/27/2019 2ND GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN IN FULL, NUMBER, ST. CITY AND ZIP CODE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. GAS RISER DIAGRAM NEED TO BE ALL IN ONE PAGE, PLEASE
 SHOW REGULATOR, UNIONS, DRIP LEGS VALVES, HARD CAP OFF
 FOR FUTURE AND CLEARLY SHOWS THE LENGTH OF ALL CUT
 SECTIONS OF PIPE PER THE 2017 FBC RES. SECS. G2413.4.1,
 G2413.4.2.
 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE ISOMETRIC PER THE 2017 FBC RES. SEC. G2413.2.
 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC.
 G2420.4.
 5. THIS TANKLESS UNIT CALLS FOR A LOWER WATER COLUMN
 AND IF THE SERVICE METER DISCHARGES IS A 2 PSI WATER
 COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
 6. SUBMIT SPEC THAT SHOW THE POOL HEATER SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82% PLEASE PER THE 2017
 FBC-ENERGY SEC. R403.10.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  