2019-09-27 17:17:21 | 09/27/2019 2ND GAS REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE |
| ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE |
| SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED |
| ON THE RESUBMITTAL REVIEW. |
| |
| 1. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON |
| PLAN IN FULL, NUMBER, ST. CITY AND ZIP CODE PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 2. GAS RISER DIAGRAM NEED TO BE ALL IN ONE PAGE, PLEASE |
| SHOW REGULATOR, UNIONS, DRIP LEGS VALVES, HARD CAP OFF |
| FOR FUTURE AND CLEARLY SHOWS THE LENGTH OF ALL CUT |
| SECTIONS OF PIPE PER THE 2017 FBC RES. SECS. G2413.4.1, |
| G2413.4.2. |
| 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE ISOMETRIC PER THE 2017 FBC RES. SEC. G2413.2. |
| 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC. |
| G2420.4. |
| 5. THIS TANKLESS UNIT CALLS FOR A LOWER WATER COLUMN |
| AND IF THE SERVICE METER DISCHARGES IS A 2 PSI WATER |
| COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| SEC. G2421.1. |
| 6. SUBMIT SPEC THAT SHOW THE POOL HEATER SHALL HAVE A |
| MINIMUM THERMAL EFFICIENCY OF 82% PLEASE PER THE 2017 |
| FBC-ENERGY SEC. R403.10.4. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |