2019-09-17 17:25:3009/17/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN IN FULL, NUMBER, ST. CITY AND ZIP CODE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. GAS RISER DIAGRAM REQUIRED AND CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER THE 2017 FBC
 RES. SECS. G2413.4.1, G2413.4.2.
 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE ISOMETRIC PER THE 2017 FBC RES. SEC. G2413.2.
 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC.
 G2420.4.
 6. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. YOU CAN USE THE HOUSE PLAN
 AND IT CAN BE HAND DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 7. PLEASE SUBMIT MANUFACTURES SPECIFICATION FOR
 APPLIANCES, I.E. DRYER, STOVE AND TANKLESS. WHAT WAS
 SUBMITTED ON THESE APPLIANCES ARE PRODUCT INFORMATION
 NOT SPECIFICATION OR AND INSTALLATIONS INSTRUCTION,
 PLEASE REFER TO THIS WEBSITE FOR A SAMPLE OF THE
 TANK-LESS (SEE LAST PAGE) PER THE 2017 FBC RES. SEC.
 G2408.1. HTTPS://WWW.AIRSOLUTIONS.CA/IMAGES/PRODUCTS/NA
 VIEN/PRODUCTS/NPE-SERIES/NAVIEN-NPE-BROCHURE.PDF
 8. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 IF THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
 9. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
 10. IF USING LOUVERS SHOW THE LOCATION OF THE LOUVERS
 THAT ARE BEING INSTALLED FOR THE COMBUSTION AIR. THE
 LOUVERS CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS
 FIRE RATED AS THE FIRE RATING OF THE WALL MUST BE
 MAINTAINED.
 11. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
 12. LABEL SHUTOFF VALVE ON GAS ISOMERIC PER THE 2017
 FBC RES. SEC. G2401.1.3.
 13. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2
 14. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC RES. SEC. G2413.2 AND G2404.3.
 15. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE
 GENERATOR AND POOL HEATER SHOW ON GAS ISOMERIC PER THE
 2017 FBC RES. SEC. G2401.1.3.
 16. SUBMIT SPEC THAT SHOW THE POOL HEATER SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82% PLEASE PER THE 2017
 FBC-ENERGY SEC. R403.10.4.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  