2019-09-11 07:53:40 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| ALL STRUCTURES INSTALLED FOR LESS THAN 180 DAYS, |
| GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS |
| * APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO WEEKS |
| PRIOR TO EVENT |
| 1. PERMIT APPLICATION |
| A. PROVIDE EVENT FUNCTION |
| B. ADDRESS OF EVENT |
| C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS |
| D. OWNER AND CONTRACTOR INFO. |
| E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER |
| F. SPECIFY DATES OF INSTALLATION AND REMOVAL |
| 2. SITE PLAN |
| A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE? |
| B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER |
| FBC CHPT. 6, SEC. 602 |
| C. PROVIDE SQUARE FOOTAGE |
| D. PROVIDE ESTIMATED OCCUPANCY CONTENT OF EACH TENT |
| E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT |
| ENTRANCE |
| F. IDENTIFY MEANS OF EGRESS PER CHPT. 10 |
| G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE |
| RESTROOMS |
| H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500 |
| FEET OF TENT |
| 2. FOUNDATION/TIE DOWN |
| A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT |
| B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL |
| MOVEMENT |
| 3. CONFORMANCE PER SECTION 3103.1.1 |
| TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| HEALTH, SAFETY AND GENERAL WELFARE. |
| A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| STRUCTURES WITH SPANS OF 30 FEET OR GREATER. |
| B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| NFPA 701 FOR EACH TENT |
| C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN |
| REQUIRED. |
| 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| A) STATE OCCUPANT LOAD. |
| B) IDENTIFY MEANS OF EGRESS. |
| C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO |
| EXIT. |
| D) PROVIDE FLOOR LAYOUT OF EVENT. |
| D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE |
| PLAN |
| E. LIGHT 1) OPEN SIDES ? N/A |
| 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| F. VENTILATION 1) OPEN SIDES ? N/A |
| 2) CLOSED SIDES ? PER SEC. 1203 |
| G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES |
| ON SITE PLAN |
| 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902. |
| _______________________________________________________ |
| _________________ |
| |
| |
| *ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 30 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| OPTION TO ABOVE REQUIREMENT ? |
| YOU MAY PLACE A STATEMENT ON YOUR PLAN THAT THE TENT |
| WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH |
| |
| _______________________________________________________ |
| _________________ |
| |
| |
| **ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 40 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| NO EXCEPTIONS |
| |
| |