Notes
Date Text
2019-11-21 17:12:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE GENERATOR AND LABOR IS TOO LOW.
  
 PLEASE SUBMIT A SIGNED CONTRACT FOR THE INSTALLATION.
  
 PAGE E-4.0.0
  
 2) ATS. #2 AND #4 CHECK WORKING CLEARANCES FROM 110.26
  
 3) F/P CONTROLLER OCP TO EMERGENCY SYSTEM?? WHAT SIZE??
  
 4) GENERATOR RISER SHOWS NO WIRE SIZES FROM GDP TO
 TRANSFER SWITCHES ECT, ECT.