2019-09-13 07:12:1509/13/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. UNDER RESIDENTIAL REMODEL PERMIT 18090030 WHEN IT
 WENT UNDER REVIEW A GAS REVIEW WAS NOT DONE AND A FULL
 REVIEW WILL BE REQUIRED, AND IT WAS ALSO NOTED THAT
 NEEDED A SEPARATE PERMIT WAS REQUIRED. THE REVIEW WAS
 NOT ADDRESSED AND AT FINAL PLUMBING INSPECTION IT WAS
 ALSO NOTED THAT A PERMIT AND INSPECTION WAS REQUIRED
 AND A PERMIT WAS PULLED WHICH HAD NO REVIEW AS GENERAL
 CONTRACTOR TOLD BUILDING DEPARTMENT THAT IT WAS NOT
 NEEDED, AS FOR FURTHER ACCESSING THE PLAN A FULL REVIEW
 IS REQUIRED WHICH WILL BE DONE UNDER THIS REVIEW PER
 WPB AMENDMENTS TO FBC SEC. 107.2.1
 2. GAS RISER DIAGRAM MISSING INFORMATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS.
 3. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
 5. PLEASE SHOW SHUTOFF VALVES, UNIONS, DRIP LEGS, BTU
 AND REGULATORS ON ISOMETRIC PER THE 2017 FBC RES. SEC.
 G2420.4.
 6. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2017 FBC FG SEC 410.2.
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
 8. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS
 9. THE PLANS INDICATE THAT THERE IS GENERATOR, IF IT
 WAS INSTALLED OR FUTURE PLEASE INDICATE. THE BTU LOAD
 OF ALL GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD
 ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY
 SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE
 REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS
 PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES PER THE 2017 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 10. SUBMIT TWO COPIES OF THE FOR THE INSTALLATION
 CLEARANCES FROM THE TANKLESS INSTALLATION MANUAL. THE
 MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12
 INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE
 LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN
 AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM
 EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 11. IF THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
 12. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR ALL TANKLESS GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2017 FBC RES. SEC. G2413.2 AND
 G2404.3.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW