Plan Review Notes
Plan Review Notes For Permit 19090173
Permit Number 19090173
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-16 10:12:36BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT:19090173 REVISION TO MASTER 19060311
 REVIEWED: SEPTEMBER 16, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 107.5.3 FBC[AMENDED]PLEASE PROVIDE A NARRITIVE TO
 EXPLAIN WHAT IS OCCURING IN THE REVISION. SHEET D-2 NOW
 SHOWS UNIT OPEN TO PREVIOUS AGJACENT TENANT SPACE A12
 AND NOTES CALL TO REMOVE THE NEXT DEMISING WALL.
 SHEET A-1 SHOWS REMOVING THE DOOR THAT COMMUNICATED
 WITH ADJACENT AND REMOVING WALL IN ADJACENT UNIT. WHY
 SHOW NEW SPACE ADDED TO ADJACENT TENANT.
 IF SPACE IS ADDED TO THAT UNIT THAN PROVIDE SEPARATE
 PERMIT WITH DOCUMENTATION TO SHOW HOW THAT UNIT IS
 BEING ALTERED TO ADD ADDITIONAL SPACE TO INCLUDE LIFE
 SAFETY AND FLOOR PLAN.
  
 2) 107.5.3 FBC[AMENDED]IS CASPER BECOMING LARGER THAN
 PREVIOUSLY PERMITTED, OR DOES THE SHEET A-1 PROJECT
 AREA INCLUDE AREA FROM THE ADJACENT TENANT.
 PROVIDE AN UPDATED OCCUPANT LOAD THAT WAS PREVIOUSLY
 FOUND IN MASTER ON SHEET T-001 IF APPLICABLE.
  
 3) 107.5.3 FBC[AMENDED]WHAT IS THE CURRENT USE OF
 ADDITIONAL SPACE BEING ADDED FOR WHAT TENANT AND THE
 PROPOSED USE?(MAY REQUIRE ADDITIONAL PERMIT IF IS
 ADDING SPACE TO THE ADJACENT TENANT)
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  