2019-09-17 16:09:1509/17/2019 1ST GAS/LP/TANK REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW ALL UNIONS IN FRONT OF SECOND STAGE
 REGULATOR 1? OF EITHER SIDE PER THE 2017 FBC FG SEC
 410.2.
 2. SHOW THE DEPTH OF THE LP GAS CONTAINER IF BELOW
 GRADE. COMPLY WITH NFPA 58 SEC. 6.6.6.1.
 3. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN INCLUDING CITY. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. IN THE UNDERGROUND UNIT CLEARLY INDICATE ON TIE-DOWN
 SHEET WHICH IS THE LP TANK TIE-DOWN METHOD AND IF YOU
 ARE USING STRAPS OR CABLE, IF CABLE HOW IS IT PROTECTED
 FOR THE LP TANK AND APPURTENANCES PER NFPA 58. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 5. ON THE TIE-DOWN SPECS A COPY OF SIGNATURE OR SEAL IS
 NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE PER
 61G15-23.001, FLORIDA STATUTE 471. PLEASE PROVIDE THE
 DOCUMENT FOR YOUR TIE DOWN WITHOUT A SEAL AND
 SIGNATURE, NO COPIES.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  