2019-09-17 10:56:36 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | | SEE REDLINED COMMENTS ON PLAN SHEET A.05 | | 1 - DELETE CLOUDED TUB VENT; IT DOES NOT FIT THE PLAN | | VIEW FOOTPRINT AND IS NOT REQUIRED | | 2 - DELETE CLOUDED SHOWER DRAIN; THE DRAIN IS S-TRAPPED | | AND IS PROHIBITED PER FBC RES P3105.2, P, P3201.5 AND | | EXCEEDS THE MAXIMUM ALLOWABLE LENGTH FROM TRAP TO VENT | | AS STATED IN FBC RES TABLE P3105.1. | | 3 - CONNECT SHOWER DRAIN TO WET VENT AS RED LINED; WET | | VENT TO BE SIZE 3? BETWEEN TUB AND SHOWER CONNECTIONS. | | 4 - WATER CLOSET IS RELOCATED AND SHALL BE SHOWN PER | | WPB FBC 107.2.1 |
|