2019-09-17 10:56:36PLUMBING COMMENTS: APPROVED W/PROVISO
  
 SEE REDLINED COMMENTS ON PLAN SHEET A.05
 1 - DELETE CLOUDED TUB VENT; IT DOES NOT FIT THE PLAN
 VIEW FOOTPRINT AND IS NOT REQUIRED
 2 - DELETE CLOUDED SHOWER DRAIN; THE DRAIN IS S-TRAPPED
 AND IS PROHIBITED PER FBC RES P3105.2, P, P3201.5 AND
 EXCEEDS THE MAXIMUM ALLOWABLE LENGTH FROM TRAP TO VENT
 AS STATED IN FBC RES TABLE P3105.1.
 3 - CONNECT SHOWER DRAIN TO WET VENT AS RED LINED; WET
 VENT TO BE SIZE 3? BETWEEN TUB AND SHOWER CONNECTIONS.
 4 - WATER CLOSET IS RELOCATED AND SHALL BE SHOWN PER
 WPB FBC 107.2.1