Date |
Text |
2019-10-08 14:45:21 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. WPB A 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING |
| PLANS SHALL BE DRAWN TO A MINIMUM 1/8-INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| 2.FBC B 107.2.1. PLEASE PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION ON SUBMITTED DRAWINGS: |
| CONSTRUCTION TYPE; WIND DESIGN CRITERIA; CLASSIFICATION |
| OF WORK (LEVEL 2 ALTERATION); CODE REFERENCE; OCCUPANCY |
| GROUP; BUILDING HEIGHT; EXPOSURE CATEGORY. |
| 3.FBC EB 801.1 & 801.2 LEVEL 2 ALTERATIONS AS DESCRIBED |
| IN SECTION 504 SHALL COMPLY WITH THE REQUIREMENTS OF |
| CHAPTER 8. IN ADDITION TO THE REQUIREMENTS OF THIS |
| CHAPTER, ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| CHAPTER 7. |
| 4.FBC B 107.2.1 PROVIDE AN EXISTING AND PROPOSED |
| EXTERIOR ELEVATION DRAWING DETAIL OF ALL WORK AREAS. |
| 5.FBC B 107.2.1 PROVIDE AN EXISTING AND PROPOSED FLOOR |
| PLAN AND PROVIDE DIMENSIONS; DEMO INFORMATION. |
| 6.FBC B 107.2.1 PROVIDE FRAMING DETAILS SUPPLIED FOR |
| ALL NEW WALLS/CEILINGS/INFILLS/SOFFITS. SHOW ANCHORAGE, |
| BRACING AND BLOCKING |
| 7.FBC EC R503.1.1. BUILDING ENVELOPE ASSEMBLIES THAT |
| ARE PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5. |
| PROVIDE A DRAWING DETAIL SHOWING COMPLIANCE. |
| 8.FBC R R402.2 PROVIDE CONCRETE REPAIR DETAIL SHOWING |
| COMPLIANCE WITH R608.5.1. |
| 9.FBC EB 801.3 (4) ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| THE MINIMUM CEILING HEIGHT OF THE NEWLY CREATED |
| HABITABLE AND OCCUPIABLE SPACES AND CORRIDORS SHALL BE |
| 7 FEET (2134 MM). PROVIDE DETAIL SHOWING COMPLIANCE. |
| 10.FBC R R703 EXTERIOR WALL COVERINGS MUST COMPLY WITH |
| SECTION 703. PROVIDE DRAWING DETAIL SHOWING COMPLIANCE. |
| |