2019-10-08 07:51:27 | PLUMBING 1ST REVIEW**DENIED** |
| 1) ON SHT. G-103 THE MIRROR MOUNTING MAX OF 40? IS TO |
| THE REFLECTIVE SURFACE AND NOT TO ANY TRIM OR BOTTOM OF |
| THE MIRROR. FBC-ACC 603.3 |
| 2) ON SHT. G-103 THE GRAB BAR DETAIL SHOWING MOUNTING |
| OF 36? TO THE CENTER OF THE BAR IS NOT CORRECT. THE |
| MOUNTING MEASUREMENT OF ALL GRAB BARS IS 33?TO 36? TO |
| THE TOP OF THE GRAB BAR. FBC-ACC 609.4 |
| 3) ON SHT. G102 I AM UNABLE TO LOCATE THE FIXTURES |
| TOTALS YOU CALL OUT. PLEASE CLARIFY AND GAVE A |
| NARRATIVE AND LOCATION. THE TOTAL TOILET AND SINKS BOTH |
| MEN AND WOMENS ARE LESS THEN CALLED OUT. SAME WITH |
| DRINKING FOUNTAIN AND SERVICE SINKS. FBC 107.2.1 |
| 4) THE TOILET GANG BATHROOMS #104 AND #105 ARE SHOWN AS |
| OUTSIDE OF SCOPE OF WORK ON DEMO SHT. AD-100 BUT ON |
| OTHER SHEETS WORK IS CALLING TO BE PERFORMED IN THIS |
| ROOMS. PLEASE CLARIFY. FBC 107.2.1 |
| 5) PROVIDE ALL TOILET ROOM DIMENSIONS. FBC 107.2.1 |
| 6) PROVIDE TOILET COMPARTMENT ROOMS CLEAR FLOR SPACE |
| AND TURNING SPACE ON SHT. A-420. FBC-107.3.5 |
| 7) PER SHT. G-102 YOU PROVIDE THE OCCUPANT LOAD AS |
| 12.69 BUT ONLY PROVIDE 12 TOILETS. PER FBC 2902.1.1 |
| FRACTIONAL NUMBERS RESULTING FROM APPLYING THE FIXTURE |
| RATIOS OF TABLE 2902.1 SHALL BE ROUNDED UP TO THE NEXT |
| WHOLE NUMBER. FOR CALCULATIONS INVOLVING MULTIPLE |
| OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR EACH OCCUPANCY |
| SHALL FIRST BE SUMMED AND THEN ROUNDED UP TO THE NEXT |
| WHOLE NUMBER. |
| 8) SHOW THAT THE DISHWASHER AND REFRIGERATOR/ FREEZER |
| WILL MEET FLORIDA ACCESSIBILITY SECTIONS 804.6, |
| 804.6.3, 804.6.6 |
| |