2019-10-08 07:51:27PLUMBING 1ST REVIEW**DENIED**
 1) ON SHT. G-103 THE MIRROR MOUNTING MAX OF 40? IS TO
 THE REFLECTIVE SURFACE AND NOT TO ANY TRIM OR BOTTOM OF
 THE MIRROR. FBC-ACC 603.3
 2) ON SHT. G-103 THE GRAB BAR DETAIL SHOWING MOUNTING
 OF 36? TO THE CENTER OF THE BAR IS NOT CORRECT. THE
 MOUNTING MEASUREMENT OF ALL GRAB BARS IS 33?TO 36? TO
 THE TOP OF THE GRAB BAR. FBC-ACC 609.4
 3) ON SHT. G102 I AM UNABLE TO LOCATE THE FIXTURES
 TOTALS YOU CALL OUT. PLEASE CLARIFY AND GAVE A
 NARRATIVE AND LOCATION. THE TOTAL TOILET AND SINKS BOTH
 MEN AND WOMENS ARE LESS THEN CALLED OUT. SAME WITH
 DRINKING FOUNTAIN AND SERVICE SINKS. FBC 107.2.1
 4) THE TOILET GANG BATHROOMS #104 AND #105 ARE SHOWN AS
 OUTSIDE OF SCOPE OF WORK ON DEMO SHT. AD-100 BUT ON
 OTHER SHEETS WORK IS CALLING TO BE PERFORMED IN THIS
 ROOMS. PLEASE CLARIFY. FBC 107.2.1
 5) PROVIDE ALL TOILET ROOM DIMENSIONS. FBC 107.2.1
 6) PROVIDE TOILET COMPARTMENT ROOMS CLEAR FLOR SPACE
 AND TURNING SPACE ON SHT. A-420. FBC-107.3.5
 7) PER SHT. G-102 YOU PROVIDE THE OCCUPANT LOAD AS
 12.69 BUT ONLY PROVIDE 12 TOILETS. PER FBC 2902.1.1
 FRACTIONAL NUMBERS RESULTING FROM APPLYING THE FIXTURE
 RATIOS OF TABLE 2902.1 SHALL BE ROUNDED UP TO THE NEXT
 WHOLE NUMBER. FOR CALCULATIONS INVOLVING MULTIPLE
 OCCUPANCIES, SUCH FRACTIONAL NUMBERS FOR EACH OCCUPANCY
 SHALL FIRST BE SUMMED AND THEN ROUNDED UP TO THE NEXT
 WHOLE NUMBER.
 8) SHOW THAT THE DISHWASHER AND REFRIGERATOR/ FREEZER
 WILL MEET FLORIDA ACCESSIBILITY SECTIONS 804.6,
 804.6.3, 804.6.6
  
 TIM HUNT
 PLUMBING PLANS EXAMINER