Plan Review Notes For Permit 19090022 |
Permit Number |
19090022 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-10-09 09:20:37 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19090022 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-801: REFER TO SECTION 809.2 FBC EX AND | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS | | AND SPACES INVOLVED IN THE 1ST AND 2ND FLOOR | | ALTERATIONS. PROVIDE A SCHEDULE THAT INDICATES THE | | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR PER TABLE | | 403.3.1.1 FBC M. PLEASE ADD THE O/A CFMS MISSING IN THE | | AIR HANDLING SCHEDULE. | | | | 2) M-202, A-202: PROVIDE ACCESS PANELS FOR VAV'S 2-6, | | 2-7, 2-21 LOCATED ABOVE GYPSUM CEILINGS- SECTION 306.1 | | FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|