Plan Review Notes
Plan Review Notes For Permit 19090022
Permit Number 19090022
Review Stop B
Sequence Number 1
Notes
Date Text
2019-10-21 10:49:022017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090022
 ADD: 2751 S. DIXIE HWY.
 CONT: RED DOOR CONSTRUCTION LLC
 TEL: 786-535-1006
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 16/ 2019
 ACTION: DENIED
  
 1) WHEN VIEWING THE ADDRESS OF 2751 S DIXIE HWY THERE
 ARE 6 LOTS THAT APPEAR UNDER THIS ADDRESS AND ONE LARGE
 BUILDING? FIVE OF THE 6 LOTS HAVE LOT LINES THAT
 TRANSGRESS THROUGH THE BUILDING, EITHER THERE ARE FIRE
 WALLS WITH FIRE DOORS AT EACH PROPERTY LINE OR A UNITY
 OF TITLE IS REQUIRED. PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THIS BUILDING. NOTE THIS EXERCISE MAY
 HAVE BEEN COMPLETED UNDER PREVIOUS PERMITS. WHEN THE
 CITY SUBMITS THE UNITY OF TITLE TO THE CLERK OF THE
 COURT AT THE COUNTY COMPLEX THEIR OFFICE (CLERK OF THE
 COURT) DOES NOT FORWARD THIS DOCUMENT TO THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE SO THEY NEVER UPDATE
 THEIR RECORDS.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. SEE WEBSITE
 FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 2) WE THANK YOU FOR THE NARRATIVE AS TO THE WORK TO BE
 PERFORMED UNDER THIS PERMIT BUT THERE ARE TWO CONCERNS
 THAT WE HAVE.
 2A)(1) ON THE 1ST FLOOR LIFE SAFETY PLAN ONLY ONE STAIR
 IS SHOWN STAIR # 1. ON THE 2ND FLOOR LIFE SAFETY PLAN
 THE 2ND STAIRWAY IS SHOWN. THE PLANS (1ST FLOOR LIFE
 SAFETY PLAN) DOES SHOW COMPLIANCE WITH SECTION 1028.1
 EXCEPTION 1.1 WHERE NOT MORE THAN 50% OF THE NUMBER OF
 REQUIRED EXITS CAN TRAVEL THROUGH A FREE AND
 UNOBSTRUCTED PATH OF TRAVEL TO AN EXTERIOR EXIT DOOR
 AND SUCH DOOR IS READILY VISIBLE AND IDENTIFIABLE FROM
 THE POINT OF TERMINATION OF THE ENCLOSURE.
  
 THE 2ND FLOOR LIFE SAFETY PLAN DOES SHOW THE LOCATION
 OF STAIRWELL # 2. NEITHER STAIRWELL INDICATES THEY ARE
 FIRE RATED AND WHAT HOUR THE SHAFTS ARE RATED. IT WOULD
 APPEAR ON THE 2ND FLOOR PLAN BOTH STAIRWAYS ARE
 INTERIOR EXIT STAIRWAYS. BOTH HAVE TO BE CONSTRUCTED IN
 ACCORDANCE WITH 1023.2 OF THE 2017 FBC-B FOR 2 HOURS IN
 A FOUR STORY BUILDING.
  
 2A)(2) ON THE 1ST FLOOR STAIRWELL # TWO?S LOCATION IS
 NOT DECLARED ON THE PLAN, BUT COMPLIANCE WITH FBC.B
 1023.1 NEEDS TO BE SHOWN. SECTION 1023.1 OF THE 2017
 FBC-B DOES ALLOW FOR AN EXIT PASSAGEWAY CONSTRUCTED IN
 ACCORDANCE WITH SECTION 1024 OF THE 2017 FBC-B. PLEASE
 SHOW HOW COMPLIANCE WILL BE ACHIEVED.
  
 2B) THE 2ND FLOOR LIFE SAFETY PLAN IN CORRIDOR # 210
 HAS A NOTE THAT THE 2ND FLOOR OF BUILDING 1 A 4 STORY
 OFFICE MEETS EGRESS REQUIREMENTS AFTER THE DEMO OF
 BRIDGE BUILDING? IS THIS PART OF THIS PERMIT OR IS THIS
 WORK UNDER A SEPARATE PERMIT? 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 OF
 THE ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3A) THE 1ST FLOOR LIFE SAFETY PLAN SHOWS 2 LOUNGES AN
 ACTIVE LOUNGE # 147 OF 912 SQUARE FEET AND A PASSIVE
 LOUNGE # 149 WITH 1925 SQUARE FEET. THE ACTIVE LOUNGE
 IS SHOWN AS A BUSINESS USE WHEREAS THE PASSIVE LOUNGE
 IS BEING SHOWN AS AN ASSEMBLY USE. IT WOULD APPEAR THAT
 BOTH LOUNGES ARE AN ASSEMBLY OCCUPANCY. IT WOULD APPEAR
 THIS IS A MIXED USE 1ST FLOOR WITH BUSINESS AND
 ASSEMBLY OCCUPANCIES RATHER THAN ACCESSORY OCCUPANCIES,
 SEE SECTION 508.2.3 OF THE 2017 FBC-B. WHEN THE PASSIVE
 AND ACTIVE SQUARE FOOTAGE ARE COMBINED THEY ADD UP TO
 2837 SQ. FEET OR OVER 10 % OF THE 1ST FLOOR AREA.
  
 3B) THE DESIGNER OF RECORD WILL NEED TO PROVIDE DESIGN
 CRITERIA FOR EITHER NON-SEPARATED OCCUPANCIES UNDER
 508.3 OR 508.4 SEPARATION OF OCCUPANCIES IN COMPLIANCE
 WITH 508.2.4.
  
 3C) THE OCCUPANCY COUNT WOULD NEED TO BE REVISED FOR
 THE ACTIVE LOUNGE TO 15 SQ. FT. PER OCCUPANT, SEE 2017
 FBC-B TABLE 1004.1.2.
  
 4) THE 1ST FLOOR LIFE SAFETY PLAN SHOWS THE ROOM USAGE
 FOR THE ACTIVE LOUNGE ROOM 147 AND 912 SQ. FT. BUT THE
 ROOM IDENTIFICATION TAG IS NOT OVER THE LOUNGE. THERE
 IS NO ROOM IDENTIFICATION TAG FOR THE AREA IN FRONT OF
 THE ROOM, LEASABLE SPACE 143 UNLESS THE SQ. FOOTAGE FOR
 THE LEASABLE SPACE IS INCLUDES THE ROOM NOT IDENTIFIED?
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
  
 5A) BOTH THE 2ND FLOOR LIFE SAFETY PLAN AND THE LEVEL 2
 FLOOR PLAN SHOW A 2 STORY ATRIUM. THE 2ND LEVEL FLOOR
 PLAN NOTE 33 INDICATES TO REPAIR EXISTING LOW WALL AND
 WINDOW FRAME. THE PLANS DO NOT HAVE A SECTION THROUGH
 THIS AREA NOR HOW COMPLIANCE WITH 404.6 ENCLOSURES OF
 ATRIUMS OF THE 2017 FBC-B IS TO BE COMPLIED WITH. SEE
 404.6 AND EXCEPTIONS.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5B) DOES THE EXISTING CONFERENCE ROOM ##211 AND THE
 FUTURE TENANT SPACE 260 SHARED ATRIUM WALLS ALSO COMPLY
 WITH SECTION 404.6 AND OR EXCEPTIONS.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 6) DISCREPANCY IN PLANS BOTH B102 LEVEL 2 LIFE SAFETY
 PLAN AND A-102 BOTH SHOW CLOSETS 203A & 203B. SHEET
 A-102 LEVEL 2 FLOOR PLAN INDICATES A DETAIL 1/ SHEET
 A-400. IT WOULD APPEAR THE WRONG DETAIL WAS PLACED
 UNDER THIS DETAIL. THERE IS 2 RESTROOMS PLUS AN
 ELEVATOR, RESTROOM CONFIGURATION DOES NOT MATCH THAT OF
 THE FLOOR PLAN AND 2ND FLOOR LIFE SAFETY PLAN.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY IN PLANS.
  
 7) THE 2ND FLOOR LIFE SAFETY PLAN OCCUPANCY COUNT LEVEL
 2 FOR ROOM 260 THE FUTURE TENANT SPACE 260 INDICATES A
 SQ. FOOTAGE OF 3732 SQ. FT. AND AN OCCUPANT LOAD OF 37,
 YOU ALWAYS ROUND UP TO THE NEXT WHOLE NUMBER YOU DO NOT
 DROP PART OF AN OCCUPANT, YOU ALWAYS ROUND UP TO THE
 NEXT WHOLE NUMBER. BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA INFORMAL INTERPRETATION.
  
 8) SHEET A-102 THE 2ND LEVEL FLOOR PLAN, PLAN NOTE A05
 INDICATES ALIGN NEW WINDOWS BELOW EXISTING LEVEL 3
 WINDOWS. NEW WINDOWS SHALL MATCH EXISTING BUTT GLAZED
 PANEL WIDTH DIRECTLY ABOVE LEVEL 3. REFER TO SHEET
 A-803. NO SUCH SHEET WAS UPLOADED IN THIS REVIEW. THE
 PLANS GO FROM A-800 TO A-810. ADDITIONAL INFORMATION IS
 REQUIRED. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.2.1.2.
  
 8A) SHEET A-102 THE 2ND LEVEL FLOOR PLAN, PLAN NOTE A05
 INDICATES ALIGN NEW WINDOWS BELOW EXISTING LEVEL 3
 WINDOWS. NEW WINDOWS SHALL MATCH EXISTING BUTT GLAZED
 PANEL WIDTH DIRECTLY ABOVE THE LEVEL 3. PLEASE NOTE IN
 THIS REVIEW NO PRODUCT APPROVALS WERE SUBMITTED FOR THE
 NEW WINDOWS.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS
  
 8B) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 8D) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) THIS REVIEW SHEET A102 NOTE 5 INDICATED NEW WINDOWS.
 THERE WAS NO WIND DESIGN CRITERIA SUBMITTED IN THIS
 REVIEW.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 9.2. RISK CATEGORY.
  
 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 9.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 9.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 10) SHEET A-600 PLATFORM AND RAISED SEATING DETAIL.
 PLEASE INDICATE WHERE THE RAISED PLATFORM AND SEATING
 IS TO OCCUR. I COULD NOT FIND A SECTION ON THE LIFE
 SAFETY FOR THE 1ST AND 2ND FLOOR PLANS NOR THE
 ARCHITECTURAL PLAN WHERE THIS OCCURS. THE CODE ANALYSIS
 SHEET INDICATES THIS BUILDING IS CONSTRUCTION TYPE
 II-B.
  
 10A) THIS SHEET DOES NOT PROVIDE ANY DESIGN CRITERIA
 FOR THE DESIGN OF THE PLATFORM. PLEASE REVIEW THE 2017
 FBC-B TABLE 1607.1(4) & (FOOTNOTE M) FOR MINIMUM LIVE
 LOAD REQUIREMENTS.
  
 10B) THE DETAILS INDICATE THE USE OF METAL STUD
 FRAMING. THE PLANS ARE SILENT AS TO THE GAUGE TO BE
 INSTALLED FOR STRUCTURAL STUDS. 2017 FBC-B SECTIONS
 2211.1 & 2211.5 FLOOR SYSTEM DESIGN.
  
 10C) THE PLAN IS SILENT AS TO THE HEIGHT OF THE
 PLATFORM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 10D) PLEASE NOTE THIS SHEET INDICATES THE SUBSTRATE
 FLOOR SHEATHING IS TO BE 2 LAYERS OF ? INCH PLYWOOD.
 PLEASE REVIEW THE 2017 FBC-B SECTION 410.4 PLATFORM
 CONSTRUCTION AND AREA A PLATFORM CAN OCCUPY, 1/3RD THE
 MAIN FLOOR AREA. WILL THERE BE STORAGE UNDER THE
 PLATFORM?
  
 11) , ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  