2019-09-19 17:20:03 | 09/19/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE |
| USED IF NO POOL FILL IS INSTALLED AT THE METER AND |
| INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO |
| PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| FOR FURTHER DIRECTIONS. |
| |
| 2. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| MAXIMUM SYSTEM FLOW (SHOW YOUR WORK PLEASE). IDENTIFY |
| ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE |
| PUMP BEING INSTALLED ON THIS POOL. IT REQUIRES THAT THE |
| MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED |
| MAXIMUM FLOW RATE OF THE SUCTION OUTLET FITTING |
| ASSEMBLY (DRAIN COVER). THE TDH CALCULATIONS MUST |
| INCLUDE ALL THE SYSTEM COMPONENTS INCLUDING SUCTION AND |
| RETURN PIPING, FITTINGS, VALVES, HEATER, FILTER, AND |
| CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT THE PUMP PER |
| ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. |
| |
| 3. INDICATE ON THE PUMP CURVE WHICH PUMP BEING |
| INSTALLED ON THIS SYSTEM. SUBMIT A POOL PUMP CURVE THAT |
| IS ENLARGED, CLEAR IN DETAIL AND LEGIBLE PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6720 |
| |