2019-09-19 08:40:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. MATH IN PROVIDED CALCULATION IS NOT CORRECT. NEC |
| 220; FBC RE E3602.2 |
| 2. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| R314.3(4), NFPA 72:29.8.3.4 |
| 3. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS |
| SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8(A)(9); FBC RE E3902.9 |
| 4. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB |
| FBC 107.2.1 |
| 5. NOTE 3 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE E4002.14 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |