2019-10-02 08:19:49 | PLAN |
| REVIEW COMMENTS |
| |
| 3RD REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) COMPLIED. |
| |
| 2) COMPLIED. |
| |
| 3) THIS COMMENT HAS NOT BEEN ADEQUATELY ADDRESSED. THE |
| PROPOSED SYSTEM S-12 ON PAGE 21 OF 67 (FL#2533-R22) |
| REQUIRES A BASE INSULATION LAYER THAT IS MECHANICALLY |
| FASTENED TO THE STEEL ROOF DECK WITH 1 FASTENER PER 3.2 |
| SQFT. SPECIFY THE SIZE OF THE INSULATION BOARDS THAT |
| WILL BE USED ( LENGTH X WIDTH ), PROVIDE CALCULATIONS |
| THAT SPECIFY THE NUMBER OF FASTENERS PER ISO BOARD (FOR |
| EACH ROOF ZONE) AND PROVIDE A FASTENER PLACEMENT DETAIL |
| SHOWING THE REQUIRED LOCATION OF THE FASTENERS PER ISO |
| BOARD (FOR EACH ROOF ZONE). SEE RAS 117. FBC 107.2.1.2 |
| ADDITIONAL COMMENTS. |
| A) I DO SEE ON YOUR DRAWING THAT THE INSULATION PANELS |
| ARE SPECIFIED AS 2 FT X 8 FT. THERE ARE NOT ANY 2 FT X |
| 8 FT FIGURES SHOWN IN RAS 117, THEREFORE I WOULD |
| SUGGEST THAT 2 FT X 4 FT OR 4 FT X 8 FT PANELS BE USED. |
| I ALSO SEE THAT THE INSULATION IN YOUR DRAWING APPEARS |
| TO BE IN BETWEEN THE TOP FLANGES OF THE STEEL DECKING. |
| PLEASE REFER TO FBC 2017 RAS NO. 117 (#4) INSULATION |
| ATTACHMENT OVER STEEL DECKS. INSULATION PANELS ARE |
| REQUIRED TO HAVE FULL CONTACT WITH THE TOP FLANGES OF |
| THE STEEL DECKING. |
| B) I HAVE REVIEWED YOUR CALCULATIONS AND AGREE THAT |
| THEY ARE CONSISTENT WITH THE ATTACHMENT AND ENHANCED |
| FASTENING OF A CONTINUOUS BASE SHEET. HOWEVER, THIS |
| DOES NOT WORK FOR INSULATION PANELS BECAUSE THEY ARE |
| NOT CONTINOUS AND AT SOME POINTS YOU WOULD HAVE |
| FASTENERS IN THE PANEL BUTT JOINTS. (NOTE: ON PAGE 3 OF |
| YOUR REPORT THE COMPUTED FASTENER SPACING FOR THE |
| PERIMETER AND CORNER IS REQUIRED TO BE ROUNDED DOWN, |
| 8.54 INCHES SHOULD BE 8 INCHES AND 4.26 INCHES SHOULD |
| BE 4 INCHES.) SEE RAS 117 (#3.1) FOR THE REQUIRED |
| INSTALLATION OF FASTENERS AT INSULATION PANEL EDGES. |
| C) SEE RAS 117 (#9) FOR THE GENERAL EQUATION TO USE FOR |
| DETERMINING THE NUMBER OF FASTENERS FOR PERIMETER AND |
| CORNER AREAS AND SEE FIGURES 1-4 OF THIS APPLICATION |
| STANDARD FOR COMPLIANT FASTENER SPACING. |
| |
| |
| |
| |
| |
| |
| |
| |
| |