Plan Review Notes
Plan Review Notes For Permit 19081519
Permit Number 19081519
Review Stop B
Sequence Number 2
Notes
Date Text
2019-09-23 14:02:17PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEERING FOR ENHANCED FASTENING THAT WAS
 SUBMITTED IS BASED ON A WIND PRESSURE ANALYSIS USING
 ASCE 7-16. THIS STANDARD IS NOT REFERENCED BY THE FBC
 2017 SIXTH EDITION. THE 2017 FBC REFERENCES ASCE 7-10
 WHICH IS THE STANDARD THAT IS REQUIRED TO BE USED. FBC
 107.3
  
 2) THE ENGINEER'S LETTER IS ADDRESSED TO PALM BEACH
 COUNTY AND THE PROJECT IS LOCATED IN THE CITY OF WEST
 PALM BEACH. PLEASE CORRECT. FBC 107.2.1
  
 3) THE PROPOSED SYSTEM S-12 ON PAGE 21 OF 67
 (FL#2533-R22) REQUIRES A BASE INSULATION LAYER THAT IS
 MECHANICALLY FASTENED TO THE STEEL ROOF DECK WITH 1
 FASTENER PER 3.2 SQFT. SPECIFY THE SIZE OF THE
 INSULATION BOARDS THAT WILL BE USED ( LENGTH X WIDTH ),
 PROVIDE CALCULATIONS THAT SPECIFY THE NUMBER OF
 FASTENERS PER ISO BOARD (FOR EACH ROOF ZONE) AND
 PROVIDE A FASTENER PLACEMENT DETAIL SHOWING THE
 REQUIRED LOCATION OF THE FASTENERS PER ISO BOARD (FOR
 EACH ROOF ZONE). SEE RAS 117. FBC 107.2.1.2
  
  