Plan Review Notes For Permit 19081519 |
Permit Number |
19081519 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-09-23 14:02:17 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ENGINEERING FOR ENHANCED FASTENING THAT WAS | | SUBMITTED IS BASED ON A WIND PRESSURE ANALYSIS USING | | ASCE 7-16. THIS STANDARD IS NOT REFERENCED BY THE FBC | | 2017 SIXTH EDITION. THE 2017 FBC REFERENCES ASCE 7-10 | | WHICH IS THE STANDARD THAT IS REQUIRED TO BE USED. FBC | | 107.3 | | | | 2) THE ENGINEER'S LETTER IS ADDRESSED TO PALM BEACH | | COUNTY AND THE PROJECT IS LOCATED IN THE CITY OF WEST | | PALM BEACH. PLEASE CORRECT. FBC 107.2.1 | | | | 3) THE PROPOSED SYSTEM S-12 ON PAGE 21 OF 67 | | (FL#2533-R22) REQUIRES A BASE INSULATION LAYER THAT IS | | MECHANICALLY FASTENED TO THE STEEL ROOF DECK WITH 1 | | FASTENER PER 3.2 SQFT. SPECIFY THE SIZE OF THE | | INSULATION BOARDS THAT WILL BE USED ( LENGTH X WIDTH ), | | PROVIDE CALCULATIONS THAT SPECIFY THE NUMBER OF | | FASTENERS PER ISO BOARD (FOR EACH ROOF ZONE) AND | | PROVIDE A FASTENER PLACEMENT DETAIL SHOWING THE | | REQUIRED LOCATION OF THE FASTENERS PER ISO BOARD (FOR | | EACH ROOF ZONE). SEE RAS 117. FBC 107.2.1.2 | | | | |
|