Plan Review Notes For Permit 19081519 |
Permit Number |
19081519 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-09-09 09:55:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THIS ONE STORY STRUCTURE IS LOCATED IN A 170 MPH | | WINDSPEED AND THE DEFAULT EXPOSURE CATEGORY IS C. | | SYSTEM S-12 ON SHEET 21 0F 67 OF PRODUCT APPROVAL | | FL2533-R22 HAS A MAXIMUM DESIGN PRESSURE OF -45.0 PSF. | | THIS PRESSURE IS TOO LOW FOR ROOF ZONES 2 (PERIMETER) | | AND 3 (CORNER). SUBMIT TWO SETS OF SIGNED AND SEALED | | ENHANCED FASTENING CALCULATIONS. THIS ASSEMBLY IS | | MARKED WITH AN ASTERISK AND IS REQUIRED TO COMPLY WITH | | THE LIMITATIONS SET FORTH IN SECTION 2.2.10.1 OF FM | | LOSS PREVENTION DATA SHEET 1-29 (JANUARY 2016) FOR ZONE | | 2/3 ENHANCEMENTS AS SPECIFIED ON PAGE 5 OF 6 OF THE | | EVALUATION REPORT. | | | | 2) PROVIDE A COPY OF FM LOSS PREVENTION DATA SHEET 1-29 | | (JANUARY 2016). FBC 107.2.1 | | | | 3) PROVIDE TWO SETS OF ARCHITECT'S DETAILS FOR | | INSTALLION OF THE ISO BOARD AND PARAPET FLASHING | | DETAILS. | | | | | | | | |
|