2019-09-09 09:55:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS ONE STORY STRUCTURE IS LOCATED IN A 170 MPH
 WINDSPEED AND THE DEFAULT EXPOSURE CATEGORY IS C.
 SYSTEM S-12 ON SHEET 21 0F 67 OF PRODUCT APPROVAL
 FL2533-R22 HAS A MAXIMUM DESIGN PRESSURE OF -45.0 PSF.
 THIS PRESSURE IS TOO LOW FOR ROOF ZONES 2 (PERIMETER)
 AND 3 (CORNER). SUBMIT TWO SETS OF SIGNED AND SEALED
 ENHANCED FASTENING CALCULATIONS. THIS ASSEMBLY IS
 MARKED WITH AN ASTERISK AND IS REQUIRED TO COMPLY WITH
 THE LIMITATIONS SET FORTH IN SECTION 2.2.10.1 OF FM
 LOSS PREVENTION DATA SHEET 1-29 (JANUARY 2016) FOR ZONE
 2/3 ENHANCEMENTS AS SPECIFIED ON PAGE 5 OF 6 OF THE
 EVALUATION REPORT.
  
 2) PROVIDE A COPY OF FM LOSS PREVENTION DATA SHEET 1-29
 (JANUARY 2016). FBC 107.2.1
  
 3) PROVIDE TWO SETS OF ARCHITECT'S DETAILS FOR
 INSTALLION OF THE ISO BOARD AND PARAPET FLASHING
 DETAILS.
  
  
  
  