Plan Review Notes
Plan Review Notes For Permit 19081490
Permit Number 19081490
Review Stop B
Sequence Number 2
Notes
Date Text
2019-10-03 09:25:43RESIDENTIAL (R3) SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- CLEARLY IDENTIFY ALL ROOMS ON THE SKETCH PROVIDED.
 ALSO, CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE BEDROOM EGRESS REQUIREMENTS OF SEC.
 702.5 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REVISED SKETCH DOESN'T IDENTIFY THE NAME OF THE ROOM
 WHERE THE WINDOWS ARE GOING TO BE REPLACED. UNABLE TO
 VERIFY IF THIS IS A BEDROOM. IF IT IS A BEDROOM, THEN
 NEED THIS INFORMATION TO VERIFY COMPLIANCE WITH THE
 BEDROOM EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING. SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND
 TYPE AND SIZE OF PROPOSED WINDOWS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- IT IS NOT CLEAR WHAT TYPE OF WINDOWS ARE GOING TO BE
 INSTALLED. SKETCH SUBMITTED SPECIFIES SINGLE HUNG
 WINDOWS WITH FIXED TRANSOM ABOVE. BUT NOA 17-0614.14
 SUBMITTED IS FOR CASEMENT WINDOWS. CLARIFY/REVISE AS
 REQUIRED AND COORDINATE WITH ITEM #1 ABOVE. SEC.
 107.2.1 CITY AMENDMENTS. IF USING CASEMENT WINDOWS,
 THEN NOA SUBMITTED IS OK. IF USING SINGLE HUNG WINDOWS,
 THEN NEED TO PROVIDE PRODUCT APPROVAL FOR SINGLE HUNG
 WINDOWS. SEC. 61G20-3 FAC.
  
 RESPONSE:
 STILL NO CLEAR WHAT TYPE OF WINDOWS ARE GOING TO BE
 INSTALLED. REVISED SKETCH NOW SAYS PW FOR ALL WINDOWS.
 WHAT DOES PW MEANS. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20.3.001 FOR:
 A) OK
  
 ORIGINAL COMMENT:
 B) SINGLE HUNG WINDOWS. COORDINATE WITH ITEM #2 ABOVE.
  
 RESPONSE:
 STILL NO CLEAR TYPE OF WINDOWS TO BE INSTALLED.
 COORDINATE WITH ITEM #2 ABOVE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) OK
  
 IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,