Plan Review Notes
Plan Review Notes For Permit 19081475
Permit Number 19081475
Review Stop M
Sequence Number 1
Notes
Date Text
2019-09-19 17:22:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081475
 9/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2: REFER TO SECTION 602.1 FBC M: PLENUMS
 SHALL BE LIMITED TO ONE FIRE AREA. AIR SYSTEMS SHALL BE
 DUCTED FROM THE BOUNDARY OF THE FIRE AREA SERVED
 DIRECTLY TO THE AIR-HANDLING EQUIPMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  