2019-09-30 07:23:57 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19081475 |
| ADD: 1641 WORTHINGTON RD. SUITE: 200 |
| CONT: ANDERSON-MOORE CONSTRUCTION CORP. |
| TEL: 561-348-4805 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. SEPT. 30/ 2019 |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY PLAN AND SHEET A1.1 SHOWS THE |
| OVERALL DIAGONAL DISTANCE OF SUITE # 200 BUT NOT THE |
| 1/3RD THE DISTANCE BETWEEN THE EXIT DOORS. PLEASE |
| PROVIDE THE DISTANCE BETWEEN THE MAIN ENTRY DOOR (200) |
| AND DOOR # 213. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION |
| 1007.1.1EXCEPTION # 2. WHERE A BUILDING IS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 903.3.1.1. THE SEPARATION DISTANCE |
| SHALL NOT BE LESS THAN 1/3 THE OVERALL DIAGONAL |
| DIMENSION OF THE AREA SERVED. |
| |
| 2) THE PROPOSED NEWLY RECONFIGURED FORMED TENANT SPACE |
| JUST BENEATH ROOM 214 ALSO IS MISSING THE OVERALL |
| DIAGONAL DIMENSION AND THE DIAGONAL DISTANCE BETWEEN |
| THE EXISTING EXIT ACCESS DOOR AND THE PROPOSED OPENING |
| 213 A. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION |
| 1007.1.1EXCEPTION # 2. WHERE A BUILDING IS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 903.3.1.1. THE SEPARATION DISTANCE |
| SHALL NOT BE LESS THAN 1/3 THE OVERALL DIAGONAL |
| DIMENSION OF THE AREA SERVED. |
| |
| 3) DISCREPANCY IN THE PLANS SHEET A1.1 THE NEW PROPOSED |
| FRONT ENTRY DOOR IS DESIGNATED WITH A DOOR TAG 200. |
| SHEET A2.0 IN THE DOOR SCHEDULE DOOR # 200 THE DOOR IS |
| IDENTIFIED AS A 1 ? INCH WOOD DOOR IDENTIFIED AS DOOR |
| TYPE E. ON THE SAME SHEET IN THE DOOR ELEVATIONS IS |
| WHERE THE DISCREPANCY OCCURS. THE WORDING BENEATH THE |
| PICTURE INDICATES A 45 MINUTE RATED SOLID CORE WOOD |
| DOOR BUT DEPICTED IS A GLAZED DOOR. |
| DISCREPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION |
| 107.2.1.2. PLEASE REVIEW OPENING PROTECTIVES UNDER |
| FBC-B TABLE 716.5 AND &16.6. |
| |
| 4) SHEET A2.0 DOORS IDENTIFIED AS DOOR TYPE A INDICATES |
| THEY ARE TO BE RE-USED AND WITH A SIDE LITE. NEITHER |
| THE DOOR SCHEDULE NOR DOOR ELEVATIONS INDICATE WHAT |
| TYPE OF GLAZING IS IN THE SIDE-LITE. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B FOR |
| HAZARDOUS LOCATIONS, SECTION 2406.4.2 GLAZING ADJACENT |
| TO DOORS. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| 104.9.1 USED MATERIALS. THE USE OF USED, RECYCLED OR |
| RECLAIMED MATERIALS WHICH MEETS THE REQUIREMENTS OF |
| THIS CODE FOR NEW MATERIALS IS PERMITTED. |
| |
| 5) THE SAME QUESTION AS THE PLUMBING PLANS EXAMINER, |
| THE DEMOLITION PLAN AD1.1 DOES NOT SHOW THE BREAK ROOM |
| CABINETRY NOR SINK NOR IS THERE ANY NOTES UNDER THE |
| HEADING OF DEMOLITION KEYNOTES OR PLUMBING DEMOLITION |
| NOTES? ADDITIONAL INFORMATION IS REQUIRED 107.2.1.2 FOR |
| COMPLIANCE WITH: |
| |
| 5A) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR |
| SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305, |
| POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE |
| CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| EXCEPTIONS: |
| 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| BARS. |
| |
| 5B) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 5C) WORK SURFACES.2017 FBC-ACCESSIBILITY CODE 902.3 |
| HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 INCHES |
| MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |