2019-09-30 07:23:572017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081475
 ADD: 1641 WORTHINGTON RD. SUITE: 200
 CONT: ANDERSON-MOORE CONSTRUCTION CORP.
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 30/ 2019
 ACTION: DENIED
  
 1) THE LIFE SAFETY PLAN AND SHEET A1.1 SHOWS THE
 OVERALL DIAGONAL DISTANCE OF SUITE # 200 BUT NOT THE
 1/3RD THE DISTANCE BETWEEN THE EXIT DOORS. PLEASE
 PROVIDE THE DISTANCE BETWEEN THE MAIN ENTRY DOOR (200)
 AND DOOR # 213.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 1007.1.1EXCEPTION # 2. WHERE A BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 903.3.1.1. THE SEPARATION DISTANCE
 SHALL NOT BE LESS THAN 1/3 THE OVERALL DIAGONAL
 DIMENSION OF THE AREA SERVED.
  
 2) THE PROPOSED NEWLY RECONFIGURED FORMED TENANT SPACE
 JUST BENEATH ROOM 214 ALSO IS MISSING THE OVERALL
 DIAGONAL DIMENSION AND THE DIAGONAL DISTANCE BETWEEN
 THE EXISTING EXIT ACCESS DOOR AND THE PROPOSED OPENING
 213 A.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 1007.1.1EXCEPTION # 2. WHERE A BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 903.3.1.1. THE SEPARATION DISTANCE
 SHALL NOT BE LESS THAN 1/3 THE OVERALL DIAGONAL
 DIMENSION OF THE AREA SERVED.
  
 3) DISCREPANCY IN THE PLANS SHEET A1.1 THE NEW PROPOSED
 FRONT ENTRY DOOR IS DESIGNATED WITH A DOOR TAG 200.
 SHEET A2.0 IN THE DOOR SCHEDULE DOOR # 200 THE DOOR IS
 IDENTIFIED AS A 1 ? INCH WOOD DOOR IDENTIFIED AS DOOR
 TYPE E. ON THE SAME SHEET IN THE DOOR ELEVATIONS IS
 WHERE THE DISCREPANCY OCCURS. THE WORDING BENEATH THE
 PICTURE INDICATES A 45 MINUTE RATED SOLID CORE WOOD
 DOOR BUT DEPICTED IS A GLAZED DOOR.
 DISCREPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION
 107.2.1.2. PLEASE REVIEW OPENING PROTECTIVES UNDER
 FBC-B TABLE 716.5 AND &16.6.
  
 4) SHEET A2.0 DOORS IDENTIFIED AS DOOR TYPE A INDICATES
 THEY ARE TO BE RE-USED AND WITH A SIDE LITE. NEITHER
 THE DOOR SCHEDULE NOR DOOR ELEVATIONS INDICATE WHAT
 TYPE OF GLAZING IS IN THE SIDE-LITE.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B FOR
 HAZARDOUS LOCATIONS, SECTION 2406.4.2 GLAZING ADJACENT
 TO DOORS. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 104.9.1 USED MATERIALS. THE USE OF USED, RECYCLED OR
 RECLAIMED MATERIALS WHICH MEETS THE REQUIREMENTS OF
 THIS CODE FOR NEW MATERIALS IS PERMITTED.
  
 5) THE SAME QUESTION AS THE PLUMBING PLANS EXAMINER,
 THE DEMOLITION PLAN AD1.1 DOES NOT SHOW THE BREAK ROOM
 CABINETRY NOR SINK NOR IS THERE ANY NOTES UNDER THE
 HEADING OF DEMOLITION KEYNOTES OR PLUMBING DEMOLITION
 NOTES? ADDITIONAL INFORMATION IS REQUIRED 107.2.1.2 FOR
 COMPLIANCE WITH:
  
 5A) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR
 SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTIONS:
 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE
 PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK
 TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET
 BARS.
  
 5B) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5C) WORK SURFACES.2017 FBC-ACCESSIBILITY CODE 902.3
 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  