2023-04-25 12:44:36***PLEASE ADDRESS PRIOR REVIEWER'S COMMENTS AS WELL.***
  
 INSUFFICIENT SUBMITTAL:
 1. PLEASE PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE,
 THE SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY
 ALONG THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN
 VERIFY THAT THE BORE AND HANDHOLES ARE WITHIN THE
 RIGHT-OF-WAY. ALSO PROVIDE REFERENCE POLE IN SURVEY TO
 COMPARE HEIGHTS. IF WORK OCCURS OUTSIDE OF ROW PLEASE
 PROVIDE ON SURVEY PROOF OF GENERAL UTILITY EASEMENTS.
  
 2. PLEASE PROVIDE PROPOSED POLE ELEVATIONS WITHIN SITE
 PLAN.
  
 3. PLEASE PROVIDE BORE PROFILE AND DEPTHS FOR ALL
 UNDERGROUND FIBER/ELECTRICAL LINES AS WELL AS POLE
 CAISSON.
  
 4. PLEASE CONFIRM MINIMUM OF 36IN. OF CLEARANCE FOR ADA
 BETWEEN FACE OF POLE AND EDGE OF SIDEWALK.
  
 5. POLE COLOR SHALL MATCH DOWNTOWN STANDARD: RAYCAP
 INTEGRATED POLE ??? RAL 7022 (UMBRA GRAY)
  