2023-04-25 12:44:36 | ***PLEASE ADDRESS PRIOR REVIEWER'S COMMENTS AS WELL.*** | | | | INSUFFICIENT SUBMITTAL: | | 1. PLEASE PROVIDE A SURVEY, PREPARED BY A FLORIDA | | LICENSED SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, | | THE SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY | | ALONG THE ENTIRE FIBER CONDUIT PATH SO THAT STAFF CAN | | VERIFY THAT THE BORE AND HANDHOLES ARE WITHIN THE | | RIGHT-OF-WAY. ALSO PROVIDE REFERENCE POLE IN SURVEY TO | | COMPARE HEIGHTS. IF WORK OCCURS OUTSIDE OF ROW PLEASE | | PROVIDE ON SURVEY PROOF OF GENERAL UTILITY EASEMENTS. | | | | 2. PLEASE PROVIDE PROPOSED POLE ELEVATIONS WITHIN SITE | | PLAN. | | | | 3. PLEASE PROVIDE BORE PROFILE AND DEPTHS FOR ALL | | UNDERGROUND FIBER/ELECTRICAL LINES AS WELL AS POLE | | CAISSON. | | | | 4. PLEASE CONFIRM MINIMUM OF 36IN. OF CLEARANCE FOR ADA | | BETWEEN FACE OF POLE AND EDGE OF SIDEWALK. | | | | 5. POLE COLOR SHALL MATCH DOWNTOWN STANDARD: RAYCAP | | INTEGRATED POLE ??? RAL 7022 (UMBRA GRAY) | | | | CHRIS KIMMERLY, AICP | | URBAN DESIGN PLANNER | | [email protected] 561-822-1426 | | |
|