2019-09-05 16:27:35 | 09/05/2019 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A FULL ADDRESS OF THE PROJECT OR RESIDENCE MUST BE |
| ON PLANS ON PAGE 2,3,4 AND 5PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 2. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE |
| USED IF NO POOL FILL IS INSTALLED AT THE METER AND |
| INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO |
| PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| FOR FURTHER DIRECTIONS. |
| |
| 3. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| MAXIMUM SYSTEM FLOW THAT ARE LEGIBLE, EXPAND CHART ON A |
| DIFFERENT PAGE AND OR ENLARGE. THE CHAT ON PAGE THREE |
| FOR SYSTEM CURVE NUMBER DO NOT COINCIDE WHERE MARK, WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 4. THE DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM |
| FLOW DOES NOT SHOW ALL FRICTION LOSS THROUGH ALL |
| COMPONENTS, CHLORINATORS, HEATER, ETC., ON THE HAYWARD |
| CALCULATOR CHART. ASSUME THE TOTAL FRICTION LOSS WOULD |
| INCLUDE THE PIPE, FITTINGS (90-DEGREE FITTINGS, 45'S, |
| TEES) AND ALSO VALVES AND FILTER. WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, |
| 4.4.9.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |