2019-09-16 11:23:53 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC |
| 225.30; WPB FBC 107.2.1 |
| 2. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUIT. NEC 250.32; FBC RE3607.3 |
| 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE CORRECTION. NEC 225.31, |
| 225.32 |
| 4. STUDIO ELECTRICAL PLAN SHOWS THE GFI RECEPTACLE FOR |
| THE BATHROOM ON THE WALL ACROSS FROM THE BASIN, AND ON |
| THE SAME CIRCUIT AS LIVING AREA. A GFCI PROTECTED |
| RECEPTACLE OUTLET ON A 20 AMP CIRCUIT IS REQUIRED |
| WITHIN 3 FEET OF EACH BASIN. THERE CAN BE NO OTHER |
| OUTLETS. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A |
| WALL OR PARTITION THAT IS ADJACENT TO THE BASIN OR |
| BASIN COUNTERTOP, LOCATED ON THE COUNTERTOP, OR |
| INSTALLED ON THE SIDE OR FACE OF THE BASIN CABINET. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| E3901.6 |
| 5. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| 801.2, OR 901.2 AS APPLICABLE. |
| 6. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS |
| SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8(A)(9); FBC RE E3902.9 |
| 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 8. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN |
| KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION. |
| NEC 210.8; FBC RE E3902.6 |
| 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 10. FOR THE ISLAND, THE SINK INSTALLED CREATES TWO |
| SEPARATE SPACE, AND A GFCI RECEPTACLE OUTLET IS |
| REQUIRED FOR EACH. PROVIDE CORRECTION. FBC RE |
| E3901.4.4; NEC 210.52 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |