Date |
Text |
2019-09-24 08:07:10 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1.FBC B 107.2.1. PLEASE CLARIFY; PLEASE NOTE THAT WE |
| ARE ONLY PROPOSING CERAMIC TILE FLOORING INSTALLATION |
| OVER WHISPERMAT CS UNDERLAYMENT, WHICH IS GOING TO BE |
| REPLACED BY PROFLEX MAXXIM SIM 90 (SEE ATTACHED TEST |
| REPORTS), THROUGHOUT THE UNIT, EXCEPT FOR THE BALCONY. |
| WHICH PRODUCT ARE YOU PROPOSING TO USE? |
| 2. FBC B 107.2.1. PROFLEX SIM 90 TEST REPORT IS BASED |
| ON 8.0? SLAB, NO CEILING. PLEASE PROVIDE VERIFICATION |
| THAT FLOOR IS 8.0? THICK. |
| |