Plan Review Notes
Plan Review Notes For Permit 19081399
Permit Number 19081399
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-23 09:45:182017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081399
 ADD: 1105 N. DIXIE HWY.
 CONT: FINE LINE CONSTRUCTION
 TEL: 6500 GEORGIA AVE.
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 23/ 2019
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET LIST TWICE DEAD END CORRIDOR
 LENGTH IS 25 FEET. ONCE UNDER THE HEADING OF LIFE
 SAFETY REQUIREMENTS, THE 2ND TIME UNDER LIFE SAFETY
 DATA. IN NEITHER CASE DOES THE PLAN STATE WHERE THIS
 MEASUREMENT IS REFERENCED IN THE CODE?
  
 UNDER THE 2017 FBC-B FOR AN UNSPRINKLERED BUILDING,
 BUSINESS OCCUPANCY SECTION 1020.4 STATES DEAD END
 CORRIDORS SHALL BE NO LONGER THAN 20 FEET. UNDER THE
 2017 EXIST. BUILDING CODE LEVEL II ALTERATION SECTION
 805.6 THE CODE ALLOWS DEAD END CORRIDORS ARE ALLOWED TO
 BE 35 FEET WITH THE EXCEPTION TO SPRINKLERED BUILDINGS
 50 FEET THE SAME AS THE FBC-B FOR SPRINKLERED
 BUILDINGS. PLEASE UPDATE THE PLANS.
  
 2) PLEASE NOTE SHEET A-2 INDICATES CREATING NEW
 OPENINGS FOR WINDOWS AND DOORS AS WELL AS ON THE NORTH
 SIDE OF THE BUILDING STORAGE ROOM 125 THAT CROSSES THE
 PROPERTY LINE. THE EXISTING BUILDING SITS ON 1105 NORTH
 DIXIE BUT THE SAME OWNERS (JCK ENTERPRISES INC.) OWN
 THE 2 ADJACENT LOTS 1101 AND 1109. THE NEW PROPOSED
 OPENINGS ON THE SOUTH SIDE OF THE BUILDING WOULD
 VIOLATE THE AMOUNT OF ALLOWABLE OPENINGS IN TABLE 705.8
 OF THE FBC-B AND ON THE NORTH SIDE THE EXISTING
 BUILDING THE STORAGE ROOM 125 TRANSGRESSES THE PROPERTY
 LINE. PLEASE GET A UNITY OF TITLE TO MAKE THESE
 MODIFICATIONS CODE COMPLIANT.
  
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3) THIS BUILDING WAS BUILT IN 1930. ASBESTOS
 COMMERCIAL: PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT
 FROM THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 4) SHEET A-2 INDICATES THE WIND SPEED OF 170 VULT,
 EXPOSURE C WITH WORST CASE WITH PRESSURES OF 41.9+/
 56.1- PSF. WHAT THE PLAN DOES NOT STATE IF THE
 PRESSURES ARE IN VULT SINCE THE WIND SPEED IS IN VULT
 OR IF THE PRESSURES ARE STATED IN VASD? WE WOULD ASSUME
 VASD, THEY WOULD BE CORRECT FOR A MEAN ROOF HEIGHT OF
 15 FEET, ALSO AN UNKNOWN.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 ADMINISTRATIVE CODE SECTION 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) THE SUBMITTED FLORIDA APPROVAL FL# 25676 IS MISSING
 THE FRONT COVER SHEET. PLEASE NOTE THIS APPROVAL IS FOR
 CURTAIN WALL SYSTEM HEADER AND FLOOR ANCHORS ONLY. NONE
 OF THE CHARTS HAVE BEEN IDENTIFIED. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET A-2 INDICATES NEW DOUBLE DOORS, LARGE MISSILE
 IMPACT DOOR AND A NEW REAR DOOR OPENING WITH METAL DOOR
 NORTH WALL. SOUTH WALL INDICATES NEW DOOR OPENING,
 LARGE MISSILE IMPACT AND METAL DOOR. THIS REVIEW NO
 PRODUCT APPROVALS FOR DOORS WERE SUBMITTED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS.
  
 7) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) THE LIFE SAFETY PLAN, SHEET A-2 FLOOR PLAN NOR THE
 SHEET A-4 THE REFLECTIVE CEILING PLAN SHOW EXIT LIGHTS.
 THE ELECTRICAL SHEET E1 THE LIGHTING FLOOR PLAN DOES
 INDICATE 3 EXIT LIGHTS. NONE OF THE ARCHITECTURAL
 SHEETS SHOW COMPLIANCE WITH REQUIRED SIGNAGE FOR
 NON-ACCESSIBLE ENTRANCES/ EXITS. STEP/ LANDING JUST
 WITHIN THE DOORWAY.
 2017 FBC-ACCESSIBILITY CODE SECTION 216.6 ENTRANCES.
 WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES
 COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT
 INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING
 WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT
 COMPLY WITH 404.
  
 10) SHEET ID-5 DETAIL: 18 SHOWS A BUILT IN SHELF WITH
 THE UPPER BREAK ROOM CABINETS. THE BOTTOM OF THE SHELF
 IS AT A HEIGHT OF 56 INCHES FROM FINISH FLOOR. THE
 ELECTRICAL SHEETS ( E2 & E3) INDICATE A RECESSED OUTLET
 ABOVE THE SHELF FOR A SMALL APPLIANCE OUTLET. THE
 PROPOSED LOCATION FOR THE SMALL APPLIANCE OUTLET DOES
 NOT COMPLY WITH THE ACCESSIBILITY CODE FOR:
 308 REACH RANGES
 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 AND POSSIBLY FOR :
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 11) SHEET ID-2 SHOWS THE RECEPTION DESK BUT THE PLAN
 DOES NOT SHOW WHERE THE CLEAR FLOOR SPACE (30 X 48
 INCHES) FOR AN ACCESSIBLE COUNTER. ACCESS. CODE 904.4
 EXCEPTION 904.4.1 OR 904.4.2.
  
 12) SHEET ID-3 & 4:
 12A) PLEASE NOTE ON THIS SHEET ALL OF THE WATER CLOSET
 GRAB BARS THE MEASUREMENTS ARE TAKEN CENTER LINE OF THE
 BAR TO THE FLOOR.
 GRAB BARS/ RESTROOMS. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 12B) DETAILS 6 & 8 THE TOILET PAPER DISPENSER DOES NOT
 SHOW COMPLIANCE WITH 2017 FBC-ACCESS. CODE 604.7
 DISPENSERS AS DIMENSIONED. TOILET PAPER DISPENSERS.
 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
 12C)(1) ALL OF THE RESTROOM ELEVATION DETAILS SHOW TILE
 WALLS TO A HEIGHT OF 40 INCHES/ 3 FEET 4 INCHES. PLEASE
 SHOW COMPLIANCE WITH THE 2017 FBC-B:
 1210.2.2 WALLS AND PARTITIONS. WALLS AND PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 12C)(2) THIS REVIEW, I DIDN?T SEE NOTATION FOR THE TILE
 SUB-BASE IN THE RESTROOMS AND OR BATHROOMS AND
 COMPLIANCE WITH THE 2017 FBC-B SECTION:
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALL AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S RECOMMENDATIONS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURER?S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
  
 12D) SHEET ID-4 PRIVATE WATER CLOSET & SHOWER DOES NOT
 REQUIRE GRAB BARS IT DOES REQUIRE THE PLACEMENT OF
 BACKING FOR THE INSTALLATION OF FUTURE GRAB BARS.
 PLEASE REVIEW THE 2017 FBC-ACCESS. CODE SECTION 604.5
 EXCEPTION # 1 & 608.3 EXCEPTION # 1.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  