2019-09-16 12:09:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SCOPE OF WORK NOT CLEAR ON PLAN. EVERYTHING IS |
| LABELED AS EXISTING. WHAT IS BEING PROPSED AS WORK? THE |
| STATEMENT ON THE PLAN JUST STATES ELECTRICAL. ALL |
| ELECTRICAL? SOME ELECTRICAL? MARK ALL ITEMS ON PLAN AS |
| NEW OR EXISTING. PROVIDE COY OF CONTRACT WHICH STATES |
| THE INCLUDED WORK AND VALUE. WPB FBC 107.2.1, 109.3 |
| 2. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR |
| THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| 107.1, 107.2.1, 107.3.5.1.2 |
| 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC |
| 215.5; WPB FBC 107.2.1 |
| 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| 6. IS THERE ANY LOAD BEING ADDED? PROVIDE ACCURATE LOAD |
| CALCULATION FOR SERVICE, INCLUDE EXISTING AND NEW LOADS |
| TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, |
| 220, 408.30; FBC RE E3602.2 |
| 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES |
| NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| NEC 210.52(C)(1); FBC RE E3901 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |