Plan Review Notes For Permit 19081310 |
Permit Number |
19081310 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-09-06 06:34:19 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE DRINKING FOUNTAINS AND THE | | SHOWERS. WPB AMEND. TTO FBC SEC. 107.2.1. | | 2) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2017 | | FBC-ACCESSIBILITY SECS.211.1, 211.2, 602. | | 3) ONE OF THE SHOWERS SHALLL COMPLY WITH 2017 FBC- | | ACCESSIBILITY SEC.309. AND BE ON AN ACCESSIBLE ROUTE | | AND COMPLY WITH FBC-ACCESS. SECS. 402, 403. SHOW THE | | HEIGHT OF THE CONTROLS FOR THE SHOWER ON THE PLANS. | | 4) IDENTIFY THE LOCATIONS OF BOTH DRINKING FOUNTAINS ( | | A & B ) ON SHT. C5.00. | | 5) THE DRINKING FOUNTAINS SHALL CONNECT TO THE DRAINAGE | | SYSTEM PER THE 2017 FBC-PLUMBING SEC. 301.3. | | 6) SHOW THE SIZE OF THE DRINKING FOUNTAIN DRAIN ON THE | | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. COMPLY WITH 2017 | | FBC-PLUMBING TABLE 710.1(1). | | 7 SUBMIT A PLUMBING PERMIT APPLICATION FROM A LICENSED | | PLUMBING CONTRACTOR FOR THIS WORK. THIS IS TO BE A | | SSTAND ALONE PLUMBING PERMIT, NOT A REVISION. A GENERAL | | CONTRACTOR CANNOT BE ISSUED THIS PERMIT AS IT FALLS | | OUTSIDE THE SCOPE OF THEIR LICENSE PER FL. STATUTE 489. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|