Plan Review Notes For Permit 19081220 |
Permit Number |
19081220 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-29 11:50:44 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THERE IS ONLY ONE HORN STOBE INDICATED WITH EACH | | UNIT, WHICH MAY NOT MEET THE DECIBEL LEVELS AT THE | | PILLOW HEIGHT PER NFPA 72 | | | | PER NFPA 72 | | | | 18.4.5 SLEEPING AREA REQUIREMENTS. | | 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO | | PROVIDE | | SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND | | LEVEL OF AT | | LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 | | DB | | ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT | | LEAST | | 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, | | WHICHEVER IS | | GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA | | REQUIRED TO BE | | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). | | 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR | | RETRACTABLE | | PARTITION, IS LOCATED BETWEEN THE NOTIFICATION | | APPLIANCE AND | | THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED | | WITH THE | | BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW. | | | | PLEASE ENUSRE COMPLIANCE AND PROVIDE REVISIONS AS | | APPLICABLE BEFORE FINAL INSPECTIONS, | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|