2019-08-26 17:10:28 | 08/26/2019 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR RANGE GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| |
| 2. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| FBC RES. SECS. G2413.2 AND G2404.3. |
| |
| 3. THIS TANKLESS UNIT CALL FOR 10.5? WATER COLUMN AND |
| THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| SEC. G2421.1. |
| |
| 4. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 |
| FBC RES. SEC. G2419.2. |
| |
| 5. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC. G2421.2. |
| |
| 6. SHOW AND LABEL SHUTOFF VALVES ON GAS ISOMERIC PER |
| THE 2017 FBC RES. SEC. G2401.1.3. |
| |
| 7. TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE |
| COST OF ALL EQUIPMENT INCLUDING TANKLESS. PROVIDED ON |
| THE BONA FIDE CONTRACT PER THE WPB AMENDMENTS TO THE |
| FBC 109.3 BUILDING PERMIT VALUATIONS. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |