2019-10-11 16:53:14 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIALL, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. IT APPEARS THE SCOPE OF THE PLUMBING HAS BEEN |
| ENLARGED SHT. 4OF 5 STATES THE SCOPE IS REPLACEMENT OF |
| THE FIXTURE BUT IN THE SUBMITTAL PACKAGE I FOUND A 7 X |
| 11 SHEET OF PAPER THAT APPEARS TO BE FROM A PLUMBING |
| CONTRACTOR STATING THE SCOPE OF THE WORK WAS REPLACING |
| THE SEWER AND PIPING TO THE TOILET AND ALSO AL |
| UNDERGROUND PIPING SHALL BE CPVC IT IS UNCLEAR EXACTLY |
| WHAT IS BEING DONE PLEASE PROVIDE ON THE MAIN PLAN A |
| CLEAR AND COMPLETE SCOPE OF PLUMBING WORK, IF THE |
| UNDERGROUND SANITARY IS BEING REPLACED PLEASE PROVIDE A |
| SANITARY ISOMETRIC. PER WPB AMEND TO FBC ACC |
| 107.3.5.3(12) |
| |
| 2. HOW WILL THE JOB BE COMPLETED WILL THE CONCRETE BE |
| CHANNELED OUT IF SO PROVIDE A REPAIR DETAIL IF IT IS A |
| TUNNEL JOB PROVIDE A REPORT OF HOW THE HOLE WILL BE |
| BACK FILLED TO PROVIDE STRUCTURAL STABILITY FOR THE |
| HOUSE. PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |