Plan Review Notes
Plan Review Notes For Permit 19081187
Permit Number 19081187
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-16 11:09:27BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOW AND DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 2. PROVIDE SHUTTER SCHEDULE PER NOTE ON PLAN PAGE 1 OF
 5.
 FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES" OR PROVIDE ALL INFORMATION
 REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE
 FACTORS THAT APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 3. PROVIDE ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 4. DESIGNER TO SHOW LOCATION AND R VALUE OF INSULATION.
 R402.1 GENERAL (PRESCRIPTIVE).
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4.
  
 R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE).
 IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1,
 INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF
 SECTIONS R402.2.1 THROUGH R402.2.13.
  
 5. ENGINEER OF RECORD SHALL PLACE STATEMENT ON PLAN
 THAT EXISTING RAFTERS CAN SUPPORT THE ADDITION LOAD OF
 THE NEW AHU.
 M1201.1SCOPE.
 THE PROVISIONS OF CHAPTERS 12 THROUGH 24 SHALL REGULATE
 THE DESIGN, INSTALLATION, MAINTENANCE, ALTERATION AND
 INSPECTION OF MECHANICAL SYSTEMS THAT ARE PERMANENTLY
 INSTALLED AND USED TO CONTROL ENVIRONMENTAL CONDITIONS
 WITHIN BUILDINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  