2019-09-16 09:21:03 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19081168 |
| ADD: 428 CLEMATIS ST. |
| CONT: SUFFOLK |
| TEL: 561-676-4508 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. SEPT. 16TH/ 2019 |
| ACTION: DENIED |
| |
| 1) THE SITE PLAN, SHEET 005-EXTERIOR ELEVATIONS AND |
| S1.1.1 EXTERIOR ELEVATIONS SHOW WORK ON (2) BUILDINGS. |
| THE PLANS SHOW WORK ON 2 PROPERTIES, 428CLEMATIS ST. |
| (74-43-43-21-01-017-0041) AND 430 CLEMATIS ST. |
| (74-43-43-21-01-017-0042) 2 DIFFERENT PROPERTIES OWNED |
| BY 2 DIFFERENT OWNERS. THE PALM BEACH COUNTY PROPERTY |
| APPRAISER?S OFFICE SHOWS THE PROPERTY 428 CLEMATIS IS |
| OWNED BY 426 ST. I LP AND THE PROPERTY 430 CLEMATIS ST. |
| IS OWNED BY 430 CLEMATIS ST. LLC (2) DIFFERENT OWNER. |
| |
| PLEASE CONTACT VINCE NOEL THE CITY SURVEYOR ABOUT |
| INFORMATION FOR UNITY OF CONTROL WHEN THERE IS 2 |
| DIFFERENT OWNER FOR 2 PROPERTIES. |
| PHONE: 494-1040 EXT: 1096 |
| E-MAIL: [email protected] |
| |
| 2) DIGITAL NAMING CONVENTION. THERE ARE 2 SHEETS WITH |
| THE SAME NAME, EXTERNAL ELEVATIONS. THE 1ST EXTERIOR |
| ELEVATIONS IS ACTUALLY THE FLOOR PLAN. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED, DISCREPANCY IN THE |
| PLANS. PLEASE UPDATE. |
| |
| 3) SHEET S01.1 DESIGN WIND PRESSURE CHART: |
| |
| 3A) THE WIND DESIGN CHART GIVEN IS IN VULT, PLEASE |
| PROVIDE THE PRESSURES IN VASD SINCE ALL PRODUCT |
| APPROVALS SHOW TEST RESULTS IN VASD. OUR FIELD |
| INSPECTORS DO NOT HAVE THE TIME TO CALCULATE PRESSURES |
| IN THE FIELD. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 3B) THE PRESSURE THAT WERE GIVEN IN VULT APPEAR TO BE |
| GOOD WITH THE EXCEPTION OF THE ROOF NEGATIVE PRESSURES |
| IN THE EDGE ZONE, THEY APPEAR TO BE QUITE A BET LOWER. |
| PLEASE REVIEW PRESSURES FOR ROOF ZONE 2, FLAT ROOF MEAN |
| ROOF HEIGHT OF 20 FEET. 2017 FBC-B 1603.1.4 WIND DESIGN |
| DATA/ ASCE 7-10. |
| |
| 4) SHEET S3.1.1 SHOWS DETAILS 4 & 5 FOR STEEL ROOF |
| FRAMING FOR SKYLIGHTS AND FRAMING FOR ROOF FRAMING |
| MEMBERS TO BE WELDED TO BAR JOIST FOR ROOF TOP CURBS. |
| ROOF FRAMING RE-INFORCEMENT ONLY NOT THE CURBS. |
| THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| AMERICAN WELDING SOCIETY. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| |
| 5A) PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & OR ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, , |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, |
| |
| 5B) ON BOTH THE SHEETS 005-EXTERIOR ELEVATIONS AND |
| S1.1.1 THERE IS NO HORIZONTAL DIMENSION FOR THE GLAZED |
| AREAS TO BE ABLE TO DETERMINE GLAZING SIZES, NOR IS |
| THERE A VERTICAL DIMENSION PROVIDING WHERE THE |
| HORIZONTAL MULLION IS TO BE INSTALLED AND TO DETERMINE |
| GLAZING SIZES AND ASSOCIATED PRESSURES. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5C) INFORMATIONAL ONLY. NO PRODUCT APPROVALS WERE |
| SUBMITTED FOR THIS REVIEW. PLEASE NOTE THAT MOST |
| WINDOW/ STOREFRONT SYSTEMS ONLY INCLUDE MULLIONS TO A |
| HEIGHT OF 10 FEET, FOR THIS PROJECT IT WOULD APPEAR THE |
| VERTICAL MULLIONS WILL BE 12 FEET LONG AND A SEPARATE |
| MULLION PRODUCT APPROVAL MAYBE REQUIRED. |
| |
| 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 7A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 7B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |