Plan Review Notes
Plan Review Notes For Permit 19081168
Permit Number 19081168
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-16 09:21:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081168
 ADD: 428 CLEMATIS ST.
 CONT: SUFFOLK
 TEL: 561-676-4508
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 16TH/ 2019
 ACTION: DENIED
  
 1) THE SITE PLAN, SHEET 005-EXTERIOR ELEVATIONS AND
 S1.1.1 EXTERIOR ELEVATIONS SHOW WORK ON (2) BUILDINGS.
 THE PLANS SHOW WORK ON 2 PROPERTIES, 428CLEMATIS ST.
 (74-43-43-21-01-017-0041) AND 430 CLEMATIS ST.
 (74-43-43-21-01-017-0042) 2 DIFFERENT PROPERTIES OWNED
 BY 2 DIFFERENT OWNERS. THE PALM BEACH COUNTY PROPERTY
 APPRAISER?S OFFICE SHOWS THE PROPERTY 428 CLEMATIS IS
 OWNED BY 426 ST. I LP AND THE PROPERTY 430 CLEMATIS ST.
 IS OWNED BY 430 CLEMATIS ST. LLC (2) DIFFERENT OWNER.
  
 PLEASE CONTACT VINCE NOEL THE CITY SURVEYOR ABOUT
 INFORMATION FOR UNITY OF CONTROL WHEN THERE IS 2
 DIFFERENT OWNER FOR 2 PROPERTIES.
 PHONE: 494-1040 EXT: 1096
 E-MAIL: [email protected]
  
 2) DIGITAL NAMING CONVENTION. THERE ARE 2 SHEETS WITH
 THE SAME NAME, EXTERNAL ELEVATIONS. THE 1ST EXTERIOR
 ELEVATIONS IS ACTUALLY THE FLOOR PLAN.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED, DISCREPANCY IN THE
 PLANS. PLEASE UPDATE.
  
 3) SHEET S01.1 DESIGN WIND PRESSURE CHART:
  
 3A) THE WIND DESIGN CHART GIVEN IS IN VULT, PLEASE
 PROVIDE THE PRESSURES IN VASD SINCE ALL PRODUCT
 APPROVALS SHOW TEST RESULTS IN VASD. OUR FIELD
 INSPECTORS DO NOT HAVE THE TIME TO CALCULATE PRESSURES
 IN THE FIELD. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 3B) THE PRESSURE THAT WERE GIVEN IN VULT APPEAR TO BE
 GOOD WITH THE EXCEPTION OF THE ROOF NEGATIVE PRESSURES
 IN THE EDGE ZONE, THEY APPEAR TO BE QUITE A BET LOWER.
 PLEASE REVIEW PRESSURES FOR ROOF ZONE 2, FLAT ROOF MEAN
 ROOF HEIGHT OF 20 FEET. 2017 FBC-B 1603.1.4 WIND DESIGN
 DATA/ ASCE 7-10.
  
 4) SHEET S3.1.1 SHOWS DETAILS 4 & 5 FOR STEEL ROOF
 FRAMING FOR SKYLIGHTS AND FRAMING FOR ROOF FRAMING
 MEMBERS TO BE WELDED TO BAR JOIST FOR ROOF TOP CURBS.
 ROOF FRAMING RE-INFORCEMENT ONLY NOT THE CURBS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 5A) PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & OR ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, ,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 5B) ON BOTH THE SHEETS 005-EXTERIOR ELEVATIONS AND
 S1.1.1 THERE IS NO HORIZONTAL DIMENSION FOR THE GLAZED
 AREAS TO BE ABLE TO DETERMINE GLAZING SIZES, NOR IS
 THERE A VERTICAL DIMENSION PROVIDING WHERE THE
 HORIZONTAL MULLION IS TO BE INSTALLED AND TO DETERMINE
 GLAZING SIZES AND ASSOCIATED PRESSURES. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5C) INFORMATIONAL ONLY. NO PRODUCT APPROVALS WERE
 SUBMITTED FOR THIS REVIEW. PLEASE NOTE THAT MOST
 WINDOW/ STOREFRONT SYSTEMS ONLY INCLUDE MULLIONS TO A
 HEIGHT OF 10 FEET, FOR THIS PROJECT IT WOULD APPEAR THE
 VERTICAL MULLIONS WILL BE 12 FEET LONG AND A SEPARATE
 MULLION PRODUCT APPROVAL MAYBE REQUIRED.
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  