Plan Review Notes
Plan Review Notes For Permit 19081158
Permit Number 19081158
Review Stop P
Sequence Number 4
Notes
Date Text
2020-08-12 10:50:061) SHOW THE LOCATION OF THE DRINING FOUNTAINS ON THE
 ARCHITECTURAL FLOOR PLAN AND THE PLUMBING FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 3) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
 SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE PER
 FBC-BUILDING SEC. 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 4) THE BACKFLOWS FOR THE IRRIGATION SYTEM AND THE
 DOMESTIC WATE RSYSTEM WILL REQUIRE A SEPARATE PERMIT.
 MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING
 PERMIT SHALL BE SUBMITTED PRIOR TO THE INSTALLATION OF
 THESE DEVICES. THE DEVICES MUST BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR.F.S.489.103.
 5) A SEPARATE PERRMIT WILL BE REQUIRED FOR THE GREASE
 INTERCEPTOR. MANUFACTURER'S SPECIFICATIONS & DETAILS
 AND FACTORY SIZING CALCULATIONS WILL BE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE INTERCEPTOR PERMIT.
  