Plan Review Notes For Permit 19081158 |
Permit Number |
19081158 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-05-29 12:18:54 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-19081158 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FB FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE UPLOAD THE AC COOLING AND HEATING | | CALCULATIONS, DO NOT SEE THEM IN THIS VERSION. FBC FS | | 107.2.1 | | | | 2) PLEASE UPLOAD REVISED MECHANICAL SHEETS. UPDATES | | STATED IN REVIEW COMMENTS ARE NOT SHOWN ON THE | | MECHANICAL SHEETS. FBC FS 107.2.1 | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|