2020-05-29 13:30:46 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NOT COMPLIANT. THE OCCUPANT LOAD CALCULATIONS WERE |
| CORRECTED ON SHEET A0.0 TO 38 OCCUPANTS. HOWEVER, THE |
| LIFE SAFETY PLAN ON SHEET A2.0 WAS NOT CHANGED FROM 19 |
| TO 38 OCCUPANTS. PLEASE CORRECT SHEET A2.0. THE |
| OCCUPANT LOAD CALCULATIONS ARE INCORRECT. THE JUICE BAR |
| AND THE YOGA AREA ARE BOTH ASSEMBLY OCCUPANCIES. |
| THEREFORE, YOU WOULD USE THE ASSEMBLY OCCUPANT LOAD |
| FROM TABLE 1004.1.2 AND DIVIDE THE NET FLOOR AREA OF |
| EACH OF THESE TWO AREAS BY 15. BASED ON THE AREAS |
| PROVIDED, THIS GIVES YOU AN OCCUPANT LOAD OF 11 |
| (DECIMALS ALWAYS ROUND UP) FOR THE JUICE BAR AND 26 FOR |
| THE YOGA AREA. INCLUDING THE 1 OCCUPANT FROM THE |
| MECHANICAL ROOM AND BATHROOM AREAS THE TOTAL NUMBER OF |
| OCCUPANTS IS 38. BECAUSE THE OCCUPANT LOAD IS LESS THAN |
| 50, THIS IS A TYPE B OCCUPANCY PER FBC 303.1.1. |
| (ORIGINAL COMMENT FOLLOWS) SPECIFY OCCUPANCY TYPE AND |
| OCCUPANT LOAD ON THE PLANS. FBC 302 & 1004 IT APPEARS |
| THAT DUE TO SMALL SIZE BUILDING AND THE YOGA AREA THAT |
| THERE WILL BE LESS THAN 50 PERSONS WHICH WOULD ALLOW |
| THIS TO BE CLASSIFIED AS A BUSINESS OCCUPANCY. SEE |
| SECTIONS 303.1.1, 303.1.2 AND 304.1. |
| |
| 2) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH REVIEW COMMENT ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. THIS WILL ALSO HELP |
| REDUCE PLAN REVIEW TIME. |
| |
| |