Plan Review Notes
Plan Review Notes For Permit 19081158
Permit Number 19081158
Review Stop B
Sequence Number 3
Notes
Date Text
2020-05-29 13:30:46PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIANT. THE OCCUPANT LOAD CALCULATIONS WERE
 CORRECTED ON SHEET A0.0 TO 38 OCCUPANTS. HOWEVER, THE
 LIFE SAFETY PLAN ON SHEET A2.0 WAS NOT CHANGED FROM 19
 TO 38 OCCUPANTS. PLEASE CORRECT SHEET A2.0. THE
 OCCUPANT LOAD CALCULATIONS ARE INCORRECT. THE JUICE BAR
 AND THE YOGA AREA ARE BOTH ASSEMBLY OCCUPANCIES.
 THEREFORE, YOU WOULD USE THE ASSEMBLY OCCUPANT LOAD
 FROM TABLE 1004.1.2 AND DIVIDE THE NET FLOOR AREA OF
 EACH OF THESE TWO AREAS BY 15. BASED ON THE AREAS
 PROVIDED, THIS GIVES YOU AN OCCUPANT LOAD OF 11
 (DECIMALS ALWAYS ROUND UP) FOR THE JUICE BAR AND 26 FOR
 THE YOGA AREA. INCLUDING THE 1 OCCUPANT FROM THE
 MECHANICAL ROOM AND BATHROOM AREAS THE TOTAL NUMBER OF
 OCCUPANTS IS 38. BECAUSE THE OCCUPANT LOAD IS LESS THAN
 50, THIS IS A TYPE B OCCUPANCY PER FBC 303.1.1.
 (ORIGINAL COMMENT FOLLOWS) SPECIFY OCCUPANCY TYPE AND
 OCCUPANT LOAD ON THE PLANS. FBC 302 & 1004 IT APPEARS
 THAT DUE TO SMALL SIZE BUILDING AND THE YOGA AREA THAT
 THERE WILL BE LESS THAN 50 PERSONS WHICH WOULD ALLOW
 THIS TO BE CLASSIFIED AS A BUSINESS OCCUPANCY. SEE
 SECTIONS 303.1.1, 303.1.2 AND 304.1.
  
 2) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH REVIEW COMMENT ALONG
 WITH THE CITY RE-SUBMITTAL FORM. THIS WILL ALSO HELP
 REDUCE PLAN REVIEW TIME.
  
  