Plan Review Notes
Plan Review Notes For Permit 19081158
Permit Number 19081158
Review Stop P
Sequence Number 2
Notes
Date Text
2020-04-30 14:48:01REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 19081158 682 7TH ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: EXTERIOR SHOWER NOTED ON PLAN SHEET A2.0 AND
 P1.1; PER FBC PL 303.1, PLUMBING FIXTURES, DRAINS,
 APPURTENANCES AND APPLIANCES USED TO RECEIVE OR
 DISCHARGE LIQUID WASTE OR SEWAGE SHALL BE DIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE SYSTEM OF THE
 BUILDING OR PREMISES, IN ACCORDANCE WITH THE
 REQUIREMENTS OF THIS CODE. THE OUTDOOR SHOWER SHALL NOT
 CONNECT TO THE STORM DRAINAGE SYSTEM AS NOTED ON P1.1.
 PER WPB FBC 107.2.1, PROVIDE CONNECTION TO SANITARY
 THROUGH A TRAPPED AND VENTED FIXTURE DRAIN. COMPLY WITH
 APPLICABLE SECTIONS OF FBC PL CHAPTERS 7 AND 9.
 2. RE: MOP SINK WALL FINISHES; A2.2/DETAIL 3 AND 5
 PERTAIN TO THE BATHROOM. PER WPB FBC 107.21.1, CLEARLY
 AND SPECIFICALLY INDICATE ON THE PLANS COMPLIANT WITH
 FBC 1210.2.2.
 3. RE: TOILET ROOM WALL FINISHES; A2.1/DETAIL 3 DOES
 NOT COMPLY WITH FBC 1210.2.2. PER WPB FBC 107.2.1,
 PROVIDE COMPLIANCE.
 4. RE: TOILET PAPER HOLDER; A2.1/DETAIL 1 SHOWS TOILET
 PAPER HOLDER AT 7 INCHES FROM FRONT OF TOILET TO EDGE
 OF HOLDER. PER FBC ACC 604.7 THE TOILET PAPER HOLDER
 SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM FROM
 FRONT OF TOILET TO CENTERLINE OF HOLDER. PER WPB FBC
 107.2.1, INDICATE THE SAME ON THE PLANS.
 5. RE: P1.1 BACKFLOW PREVENTION SCHEDULE; PER FBC PL
 605.2, ALL DEVICES SHALL BE LEAD FREE. PER WPB FBC
 107.2.1, PROVIDE CORRECT MODEL NUMBERS FOR DEVICES
 INDICATING THEY ARE LEAD FREE. IT IS NOTED THAT THE
 SD-3 FOR THE COFFEE MAKER IS OF STAINLESS STEEL
 CONSTRUCTION AND AS SUCH IS NOT AN ISSUE.
 6. PER WPB FBC 107.2.1, PROVIDE A DETAIL OF HOW THE HOT
 WATER RETURN WILL CONNECT TO THE WATER HEATER OR TO THE
 COLD WATER INTO THE WATER HEATER. SHOW ALL VALVING.
  
 A SEPARATE PERMIT AND REVIEW IS REQUIRED FOR
 IRRIGATION.
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY
 THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 19081158 682 7TH ST
  
  
 PHONE 561-805-6715
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
  
 PLUMBING COMMENTS: DENIED
  
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 1) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER 2017
  
 FBC - BUILDING SEC. 302.
  
 2) INDICATE THE OCCUPANCY LOAD ON THE PLANS PER 2017
  
 FBC-BUILDING SEC. 1104 & TABLE 1004.1.2.
  
 3) SHT.A1.0 REFERS TO THE 2014 FBC. THE CODE IN EFFECT
  
 IS THE 2017 FBC. REVISE THE NOTE.
  
 4) SHT. A2.0 & SHT.P1.1 SHOWS AN EXTERIOR SHOWER. WHAT
  
 WILL THIS SHOWER BE USED FOR? CLARIFY ON THE PLANS. WPB
  
 AMEND. TO FBC SEC. 107.1. DETAIL 1 ON P1.1 CALLS THIS
  
 OUT AS A CONDENSATE WELL AND CONDENSATE LINE. CLARIFY.
  
 5) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
  
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
  
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
  
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE CALLS
  
 OUT FLAT PAINT. THIS DOES NOT COMPLY.
  
 6) WALLS AND PARTITIONS WITHIN 2 FEET OF WATER CLOSETS
  
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
  
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
  
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE ON
  
 SHT.A6.0 DOES NOT SPECIFY THE HEIGHT OF THE
  
 TILE.CLARIFY.
  
 7) AN UNDER THE SINK GREASE TRAP MAY BE REQUIRED.
  
 8) SHT. A2.1 - THE TOP OF THE LAVATORY IN THE TOILET
  
 ROOM SHALL BE LOCATED A MAXIMUM OF 34 INCHES TO THE TOP
  
 OF THE RIM PER 2017 FBC - ACCESS. SEC.606.3.
  
 9) A MINIMUM CLEARANCE OF 27 INCHES SHALL BE PROVIDED
  
 UNDER THE LAVATORY PER 2017 FBC SEC.306.3.
  
 10) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
  
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
  
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
  
 FLOOR OR GROUND.2017 FBC-ACCESS. SEC.603.3.
  
 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7
  
 INCHES MINIMUM AND 9 INCHES MAXIMUM FROM THE FRONT OF
  
 THE WATER CLOSET TO THE CENTERLINE OF THE DISPENSER.
  
 2017 FBC ACCESS. SEC.604.7.
  
 12) THE DISHWASHER, ICE MACHINE, AND COFFEE MACHINE
  
 SHALL BE EQUIPPED WITH AA BACKFLOW DEVICE PER 2017
  
 FBC-PLUMBING SEC.608.2, 608.3, 608.16.10,
  
 13) A RECIRCULATION LINE MAY BE REQUIRED FOR THE HOT
  
 WATER SYSTEM IF THE DEVELOPED LENGTH OF THE HOT WATER
  
 PIPING EXCEEDS 50 FEET FROM THE SOURCE OF HOT WATER TO
  
 THE FIXTURES THAT REQUIRE HOT WATER PER 2017
  
 FBC-PLUMBING SEC.607.2.
  
 14) SHT. P1.1 - SHOW THE SIZE OF THE EXPANSION TANK ON
  
 THE PLANS.
  
 15) TEMPERED WATER IS REQUIRED TO THE LAVATORY IN THE
  
 TOILET ROOM PER 2017 FBC-PLUMBING SEC.607.1, 416.5.
  
 16) SHT. IR-1 - IRRIGATION SCHEDULE - THE BACKFLOW
  
 PREVENTER FOR THE IRRIGATION SHALL BE LEAD FREE. 2017
  
 FBC-PLUMBING SEC.605.2. THE 975 XL BACKFLOW DEVICE IS
  
 NOT LEAD FREE.
  
 17) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
  
 PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY
  
 THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY
  
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
  
  
 TIM LARGE
  
 CHIEF PLUMBING INSPECTOR
  
 PLUMBING PLAN REVIEW
  
 561-805-6692
  
 [email protected]